Plan Review Notes
Plan Review Notes For Permit 13100931
Permit Number 13100931
Review Stop B
Sequence Number 1
Notes
Date Text
2013-10-26 12:23:162010 FBC
  
 DENIED BY BUILDING
  
 1) SHOW COMPLIANCE WITH FBC R311.2 EGRESS DOOR.
 AT LEAST ONE EGRESS DOOR SHALL BE PROVIDED FOR EACH
 DWELLING UNIT. THE EGRESS DOOR SHALL BE SIDE-HINGED,
 AND SHALL PROVIDE A MINIMUM CLEAR WIDTH OF 32 INCHES
 (813 MM) WHEN MEASURED BETWEEN THE FACE OF THE DOOR AND
 THE STOP, WITH THE DOOR OPEN 90 DEGREES (1.57 RAD). THE
 MINIMUM CLEAR HEIGHT OF THE DOOR OPENING SHALL NOT BE
 LESS THAN 78 INCHES (1981 MM) IN HEIGHT MEASURED FROM
 THE TOP OF THE THRESHOLD TO THE BOTTOM OF THE STOP.
 OTHER DOORS SHALL NOT BE REQUIRED TO COMPLY WITH THESE
 MINIMUM DIMENSIONS. EGRESS DOORS SHALL BE READILY
 OPENABLE FROM INSIDE THE DWELLING WITHOUT THE USE OF A
 KEY OR SPECIAL KNOWLEDGE OR EFFORT.
  
 2) SHOW COMPLIANCE WITH FBC R703.6.3
 WHERE CEMENT PLASTER (STUCCO) IS TO BE APPLIED TO LATH
 OVER FRAME CONSTRUCTION, MEASURES SHALL BE TAKEN TO
 PREVENT BONDING BETWEEN THE CEMENT PLASTER AND THE
 WATER-RESISTIVE BARRIER. A BOND BREAK SHALL BE PROVIDED
 BETWEEN THE WATER-RESISTIVE BARRIER AND THE CEMENT
 PLASTER (STUCCO) CONSISTING OF ONE OF THE FOLLOWING:
  
 1. TWO LAYERS OF AN APPROVED WATER-RESISTANT BARRIER
 MATERIAL; OR
  
 2. ONE LAYER OF AN APPROVED WATER-RESISTANT BARRIER
 OVER AN APPROVED PLASTIC HOUSE WRAP; OR
  
 3. OTHER APPROVED METHODS OR MATERIALS APPLIED IN
 ACCORDANCE WITH THE MANUFACTURER?S INSTALLATION
 INSTRUCTIONS.
  
 3) SHOW COMPLIANCE WITH FBC R806.1 VENTILATION
 REQUIRED.
 ENCLOSED ATTICS AND ENCLOSED RAFTER SPACES FORMED WHERE
 CEILINGS ARE APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF
 RAFTERS SHALL HAVE CROSS VENTILATION FOR EACH SEPARATE
 SPACE BY VENTILATING OPENINGS PROTECTED AGAINST THE
 ENTRANCE OF RAIN. EXCEPTION: ATTIC SPACES, DESIGNED BY
 A PROFESSIONAL ENGINEER OR ARCHITECT LICENSED TO
 PRACTICE IN THE STATE, DESIGNED TO ELIMINATE THE ATTIC
 VENTING.( SEE FBC R806.4)
  
 4) FBC ENERGY CONSERVATION 101.4.3 ADDITIONS,
 ALTERATIONS, RENOVATIONS OR REPAIRS.
 ADDITIONS, ALTERATIONS, RENOVATIONS OR REPAIRS TO AN
 EXISTING BUILDING, BUILDING SYSTEM OR PORTION THEREOF
 SHALL CONFORM TO THE PROVISIONS OF TABLE 101.4.1 OF
 THIS CODE AS THEY RELATE TO NEW CONSTRUCTION WITHOUT
 REQUIRING THE UNALTERED PORTION(S) OF THE EXISTING
 BUILDING OR BUILDING SYSTEM TO COMPLY WITH THIS CODE.
 TABLE 101.4.1
 NONEXEMPT EXISTING BUILDINGS
 RENOVATIONS
 MINIMUM CODE ENVELOPE, EQUIPMENT AND LIGHTING
 EFFICIENCY LEVELS SHALL BE MET FOR COMPONENTS BEING
 CHANGED.
 ENVELOPE: SECTION 402 OR 502
 EQUIPMENT: SECTION 403 OR 503, 504
 LIGHTING: SECTION 404 OR 505
  
 SHOW COMPLIANCE WITH SECTION 401.2 AND TABLE 402.1 FOR
 REQUIRED R-30 CEILING INSULATION AND R-13 UNDER FLOOR
 CAVITY INSULATION.
  
 5) SUBMIT TWO COPIES OF PRODUCT APPROVALS AS REQUIRED
 BY DCA RULE 9N-3 FOR THE EXTERIOR IMPACT RATED WINDOWS
 AND DOORS, THE ROOF COVERING MATERIAL FOR THE NEW FLAT
 ROOF AND THE SIMPSON HANGERS AND OTHER CONNECTORS.
  
 6) COMPLY WITH CITY AMENDMENT 107.3.4.1 WHICH REQUIRES
 THE PRODUCT APPROVALS TO BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD FOR THE PROJECT.
  
 7) ON SHEET S1, AN RAS 117 CALCULATION FOR ENHANCED
 FASTENING OF THE BASE SHEET FOR THE FIRESTONE FLAT
 ROOFING MATERIAL WITH NOA NO. 05-0830.10. THIS PRODUCT
 APPROVAL HAS EXPIRED AND IS NOT ACCEPTABLE. ALSO, AN
 OLDER EDITION ON ASCE 7 IS SPECIFIED. PLEASE REVISE FOR
 THE CURRENT ROOFING PRODUCT APPROVAL.
  
 8) PLEASE CLARIFY THE WALL SECTION NOTE ON SHEET S1
 THAT REFERENCES .625 " ROUGH SAWN STUCCO. IF YOU ARE
 REFERRING TO A HARDI-BOARD TYPE CEMENT PANEL, SUBMIT
 TWO COPIES OF THE PRODUCT APPROVALS FOR IT.
  
 9) PLEASE PROVIDE A RESPONSE LETTER WITH THE RESUMITTAL
 INDICATING HOW THE REVIEW COMMENTS WERE ADDRESSED. THIS
 WILL HELP EXPEDITE REVIEW TIME.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]