| Plan Review Notes For Permit 13100921 |
| Permit Number |
13100921 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-10-29 19:34:16 | 2007 FBC WITH 2009 REVISIONS | | | | | | DENIED BY PLUMBING | | | | | | 1) THE PLUMBING RISER DIAGRAM ON REVISED SHEET E-1 DOES | | | NOT MATCH THE FLOOR PLAN. THE MASTER BATH HAS A SINGLE | | | BOWL VANITY, A SHOWER IS SHOWN AT THE 1/2 BATH AND THE | | | KITCHEN SINK IS LABELED AS A VANITY. PLEASE CORRECT. | | | CITY AMENDMENTS 107.2.1 | | | | | | 2) THE SHOWER AND TUB IN THE MASTER BATH AND THE | | | WATERCLOSET AND TUB IN THE FULL BATH ARE NOT PROPERLY | | | VENTED. P3108.2 VENT CONNECTIONS. THE DRY VENT | | | CONNECTION TO THE WET VENT SHALL BE AN INDIVIDUAL VENT | | | OR COMMON VENT TO THE LAVATORY, BIDET, SHOWER OR | | | BATHTUB. IN VERTICAL WET VENT SYSTEMS, THE MOST | | | UPSTREAM FIXTURE DRAIN CONNECTION SHALL BE A DRY-VENTED | | | FIXTURE DRAIN CONNECTION. IN HORIZONTAL WET-VENT | | | SYSTEMS, NOT MORE THAN ONE WET-VENTED FIXTURE DRAIN | | | SHALL DISCHARGE UPSTREAM OF THE DRY-VENTED FIXTURE | | | DRAIN CONNECTION. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|