| Plan Review Notes For Permit 13100918 |
| Permit Number |
13100918 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-11-27 11:13:57 | BECAUSE THERE IS NO SUPPORTING DOCUMENTATION FOR THE | | | CAMERAS MENTIONED AS FIELD INSTALLED, THE SCOPE OF THIS | | | PERMIT IS LIMITED TO THE GENERATOR INSTALLATION AND | | | ASSOCIATED ELECTRICAL WORK FOR THE FUTURE APPARATUS | | | ADDRESSED ON THE PLANS. | | | ALL UNDERGROUND WORK SHALL BE INSPECTED BEFORE COVERING | | | UP. ALL UNDERGROUND SERVICE RACEWAYS SHALL HAVE THE | | | WARNING RIBBON AS REQUIRED BY NEC 300.5 READY FOR | | | INSPECTION. | | | A LOW VOLTAGE PERMIT WILL BE REQUIRED FOR THE | | | INSTALLATION OF THE CAMERA SYSTEM MENTIONED ON THE | | | SUBMITTED PLANS. | | | |
|