Notes
Date Text
2013-12-03 11:48:27THE RESPONSE OF 11-19-13 THAT LIGHTING CONTROL IS NOT
 REQUIRED BASED UPON THE DEFINITION OF BUILDING PROVIDED
 BELOW AND IN THE FBC-E VOLUME COUPLED WITH THE
 ASSERTION THAT A 1-HR RATED FIRE BARRIER CONSTITUTES A
 FIRE WALL AND THEREFORE QUALIFIES THE SPACE AS A
 SEPARATE BUILDING, IS INCORRECT..
  
 BUILDING. ANY STRUCTURE USED OR INTENDED FOR SUPPORTING
 OR SHELTERING ANY USE OR OCCUPANCY. FOR EACH PURPOSE OF
 THIS CODE EACH PORTION OF A BUILDING SEPARATED FROM
 OTHER PORTIONS BY A FIREWALL SHALL BE CONSIDERED AS A
 SEPARATE BUILDING. THE TERM ?BUILDING? SHALL BE
 CONSTRUED AS IF FOLLOWED BY THE WORDS ?OR PART
 THEREOF.?
  
 ONE MUST CONSIDER THE DEFINITION OF FIREWALL AND THE
 REQUIREMENTS OF FBC-T 706.4, BOTH PROVIDED BELOW.
  
 FIREWALL. FIRE RESISTANT WALL, HAVING PROTECTIVE
 OPENINGS, WHICH RESTRICTS THE SPREAD OF FIRE AND
 EXTENDS CONTINUOUSLY FROM THE FOUNDATION TO OR THROUGH
 THE ROOF, WITH SUFFICIENT STRUCTURAL STABILITY UNDER
 FIRE CONDITIONS TO ALLOW COLLAPSE OF CONSTRUCTION ON
 EITHER SIDE WITHOUT COLLAPSE OF THE WALL.
  
 FBC-T 706.4 REQUIRES A 3-HR RATING FOR FIRE WALLS FOR
 THE M OCCUPANCY CLASSIFICATION.
  
 FURTHER, THE ENERGY SUBMITTAL INDICATES ONE CONTROL
 POINT IS SUPPLIED FOR LIGHTING CONTROL.
  
 PLEASE REVISE THE ELECTRICAL PLAN TO DEMONSTRATE
 LIGHTING CONTROLS.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  
  
  
  