 MECHANICAL PLAN REVIEW
 PERMIT: 13100910
 ADD: 1741 PALM BEACH LAKES # E203
 CONT: TO BE DETERMINED
 TEL: (561)373-3902 CONTACT KARI NEVELLE
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON./ NOV. 18/ 2013
  
 ACTION: MECHANICAL PROVISO
 MECHANICAL APPROVED WITH EXCEPTION!
  
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 1) DISCREPANCY IN PLANS M-100 DUCT IDENTIFIED AS S-1/
 200 AS A 8 INCH DIAMETER DUCT WHEREAS SHEET M100 THE
 AIR DISTRIBUTION SCHEDULE IDENTIFIES IT AS A 6 INCH
 DIAMETER DUCT.
 2) DISCREPANCY IN PLANS M-100 DUCT IDENTIFIED AS S-3/
 200 AS A 8 INCH DIAMETER DUCT WHEREAS SHEET M100 THE
 AIR DISTRIBUTION SCHEDULE IDENTIFIES IT AS A 12 INCH
 DIAMETER DUCT.
  
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION 107.2.1.3
 ADDITIONAL INFORMATION REQUESTED, DISCREPANCY.
  
  
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676