| | MECHANICAL PLAN REVIEW |
| | PERMIT: 13100910 |
| | ADD: 1741 PALM BEACH LAKES # E203 |
| | CONT: TO BE DETERMINED |
| | TEL: (561)373-3902 CONTACT KARI NEVELLE |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: MON./ NOV. 18/ 2013 |
| | |
| | ACTION: MECHANICAL PROVISO |
| | MECHANICAL APPROVED WITH EXCEPTION! |
| | |
| | THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO |
| | CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO |
| | INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE |
| | ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE |
| | ADDITIONAL REVIEWS WITH ASSOCIATED FEES. |
| | |
| | 1) DISCREPANCY IN PLANS M-100 DUCT IDENTIFIED AS S-1/ |
| | 200 AS A 8 INCH DIAMETER DUCT WHEREAS SHEET M100 THE |
| | AIR DISTRIBUTION SCHEDULE IDENTIFIES IT AS A 6 INCH |
| | DIAMETER DUCT. |
| | 2) DISCREPANCY IN PLANS M-100 DUCT IDENTIFIED AS S-3/ |
| | 200 AS A 8 INCH DIAMETER DUCT WHEREAS SHEET M100 THE |
| | AIR DISTRIBUTION SCHEDULE IDENTIFIES IT AS A 12 INCH |
| | DIAMETER DUCT. |
| | |
| | 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION 107.2.1.3 |
| | ADDITIONAL INFORMATION REQUESTED, DISCREPANCY. |
| | |
| | |
| | |