| Plan Review Notes For Permit 13100869 |
| Permit Number |
13100869 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-11-14 08:40:48 | THE FOLLOWING ITEMS NEED TO BE CORRECTED ON THE | | | SUBMITTED DRAWINGS: | | | 1. THE ELECTRICAL PLANS DO NOT SHOW THE SCOPE OF WORK | | | 2. THE SINGLE LINE DIAGRAM TERMINATES AT THE NEW | | | TRANSFORMER, BUT NO LOAD IS INCLUDED | | | 3. KEY NOTE 3 ON PAGE E200 ADDRESS A FEEDER TO A NEW | | | MCC WHICH IS NOT SHOWN ON THE LINE DIAGRAM. | | | 4. IF ADDITIONAL WORK BEYOND THE MCC IS TO BE PART OF | | | THE SCOPE OF THIS PERMIT, IT TOO HAS TO BE SHOWN ON THE | | | SUBMITTED DRAWINGS. | | | 5. PROVIDE LOAD CALC FOR THE NEW MCC IF ANY LOADS WILL | | | BE ATTACHED THERETO. | | | 6.. PLEASE HAVE THE DESIGN PROFESSIONAL INDICATE WHAT | | | AREAS IF ANY ARE TO BE HAZARDOUS LOCATIONS, AND IF SO, | | | PROVIDE PROPER SUPPORTING DOCUMENTS FOR THE LIGHT | | | FIXTURES AND ALL ELECTRICAL APPARATUS BEING INSTALLED | | | WITHIN THIS LOCATION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO | | | CONTACT THIS OFFICE. | | | | | | SENT TO SH DESK |
|