2013-11-14 08:40:48THE FOLLOWING ITEMS NEED TO BE CORRECTED ON THE
 SUBMITTED DRAWINGS:
 1. THE ELECTRICAL PLANS DO NOT SHOW THE SCOPE OF WORK
 2. THE SINGLE LINE DIAGRAM TERMINATES AT THE NEW
 TRANSFORMER, BUT NO LOAD IS INCLUDED
 3. KEY NOTE 3 ON PAGE E200 ADDRESS A FEEDER TO A NEW
 MCC WHICH IS NOT SHOWN ON THE LINE DIAGRAM.
 4. IF ADDITIONAL WORK BEYOND THE MCC IS TO BE PART OF
 THE SCOPE OF THIS PERMIT, IT TOO HAS TO BE SHOWN ON THE
 SUBMITTED DRAWINGS.
 5. PROVIDE LOAD CALC FOR THE NEW MCC IF ANY LOADS WILL
 BE ATTACHED THERETO.
 6.. PLEASE HAVE THE DESIGN PROFESSIONAL INDICATE WHAT
 AREAS IF ANY ARE TO BE HAZARDOUS LOCATIONS, AND IF SO,
 PROVIDE PROPER SUPPORTING DOCUMENTS FOR THE LIGHT
 FIXTURES AND ALL ELECTRICAL APPARATUS BEING INSTALLED
 WITHIN THIS LOCATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT THIS OFFICE.
  