Plan Review Notes
Plan Review Notes For Permit 13100847
Permit Number 13100847
Review Stop B
Sequence Number 1
Notes
Date Text
2013-11-04 09:16:51BUILDING PLAN REVIEW
 PERMIT: 13100847
 ADD: 871 VILLAGE BLVD # 601
 CONT: PAGE CONTRACTING
 TEL: (954)868-7561
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MONDAY NOV. 04/ 2013
 ACTION: BUILDING PROVISOS:
  
 1) SHEET A2.00 THE DESIGNER INDICATES TTHE USE OF 1
 HOUR FIRE RATED TENANT SEPERATION WALLS, PLEASE PROVIDE
 COMPLIANCE WITH THE FOLLOWING :
 2010 FBC-B 713.6 FIRE WALLS, FIRE BARRIERS, FIRE
 PARTITIONS, SMOKE BARRIERS AND SMOKE PARTITIONS OR ANY
 OTHER WALL REQUIRED TO HAVE PROTECTED OPENINGS SHALL BE
 EFFECTIVELY AND PERMANENTLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE AUTHORITY
 HAVING JURISDICTION. SUCH IDENTIFICATION SHALL BE ABOVE
 ANY DECORATIVE CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING FOR FIRE AND SMOKE BARRIERS: ?FIRE
 AND SMOKE BARRIER ? PROTECT ALL OPENINGS.?
  
 2) SHEET A8.02 THE PLANS SHOW A ELEVATION VIEW OF THE
 CASH WRAP BUT NO DIMENSIONS, PLEASE COMPLY WITH: 2010
 FL ACESSIBILITY CODE 904.4 SALES AND SERVICE COUNTERS.
 SALES COUNTERS AND SERVICE COUNTERS SHALL COMPLY WITH
 904.4.1 OR 904.4.2. THE ACCESSIBLE PORTION OF THE
 COUNTER TOP SHALL EXTEND THE SAME DEPTH AS THE SALES OR
 SERVICE COUNTER TOP.
 904.4.1 PARALLEL APPROACH.
 A PORTION OF THE COUNTER SURFACE THAT IS 36 INCHES (915
 MM) LONG MINIMUM AND 36 INCHES (915 MM) HIGH MAXIMUM
 ABOVE THE FINISH FLOOR SHALL BE PROVIDED. A CLEAR FLOOR
 OR GROUND SPACE COMPLYING WITH 305 SHALL BE POSITIONED
 FOR A PARALLEL APPROACH ADJACENT TO THE 36 INCH (915
 MM) MINIMUM LENGTH OF COUNTER.
  
 EXCEPTION: WHERE THE PROVIDED COUNTER SURFACE IS LESS
 THAN 36 INCHES (915 MM) LONG, THE ENTIRE COUNTER
 SURFACE SHALL BE 36 INCHES (915 MM) HIGH MAXIMUM ABOVE
 THE FINISH FLOOR.
  
 904.4.2 FORWARD APPROACH.
 A PORTION OF THE COUNTER SURFACE THAT IS 30 INCHES (760
 MM) LONG MINIMUM AND 36 INCHES (915 MM) HIGH MAXIMUM
 SHALL BE PROVIDED. KNEE AND TOE SPACE COMPLYING WITH
 306 SHALL BE PROVIDED UNDER THE COUNTER. A CLEAR FLOOR
 OR GROUND SPACE COMPLYING WITH 305 SHALL BE POSITIONED
 FOR A FORWARD APPROACH TO THE COUNTER.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved