| Plan Review Notes For Permit 13100759 |
| Permit Number |
13100759 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-11-14 10:25:56 | RETURNED TO BIN R5 | | 2013-11-14 10:25:33 | THIS PERMIT IS BEING APPROVED WITH THE FOLLOWING | | | PROVISIOS: (MARKED ON CONTRACTOR COPY) | | | 1. ALL RECESSED LIGHTING SHALL BE SEALED OR GASKETED AS | | | REQUIRED BY FBC-ENERGY CONSERVATION SEC 402.4.5. | | | 2. THOUGH A CO DETECTOR IS INDICATED IN THE KITCHEN | | | AREA AS YOU EXIT FROM THE GARAGE, THIS DOES NOT MEET | | | THE REQUIREMENTS OF FBC-R 315. CARBON MONOXIDE | | | DETECTION IS REQUIRED WITH 10 OF THE ENTRANCE TO ANY | | | SLEEPING AREA. | | | 3. THE SUBMITTED DRAWINGS SHOW THE AHU UNIT BUT FAIL TO | | | INCLUDE THE REQUIRED DISCONNECTS FOR THE UNITS. THERE | | | SHALL BE A MINIMUM OF 3' CLEAR AREA IN FRONT OF THESE | | | DISCONNECTS. | | | 4. NEC 210.52(A)(2) STATES THAT ANY WALL SPACE GREATER | | | THAN 2' SHALL HAVE AN OUTLET. SEE CONTRACTOR COPY | | | 5. SINCE BEDROOM 4 HAS ACCESS TO A RESTROOM WITH A | | | SECOND EXIT TO THE CORRIDOR, FOR ENERGY CONSERVATION, A | | | CONVENIENCE NOTE IS MADE IN BEDROOM 4, TO INCLUDE A | | | 3WAY SWITCH AS YO EXIT TO THE RESTROOM | | | | | | ALL WORK IS SUBJECT TO FIELD INSPECTOR'S APPROVAL | | | |
|