2013-12-05 11:57:37***PROVISO***
  
 1. WATER HEATER T&P SHALL BE INSTALLED PER P504.6(1-
 13) AND PAN DRAIN SHALL BE INSTALLED PER 504.7.2
  
 2. IN THE ORIGINAL CONFIGURATION THE COMMON AREA TOILET
 FACILITIES WOULD BE OVER 500' FROM THE STORE ENTRANCE.
 P403.3.2 LOCATION OF TOILET FACILITIES IN OCCUPANCIES
 OTHER THAN COVERED MALLS.
 ALSO, THE ROUTE TO THE STORE FACILITIES IS THROUGH A
 STORAGE (STOCK) AREA.
 P403.3.1 ACCESS. IF THE MALL COMMON RESTROOMS ARE TO BE
 ACCESSED THROUGH THE EXIT CORRIDOR, PUBLIC ACCESS WILL
 BE REQUIRED AT ALL TIMES THAT THE BUILDING IS OCCUPIED.
  
 3. MALL DIRECTIONAL SIGNAGE WILL BE REQUIRED:
 403.4.1 DIRECTIONAL SIGNAGE.
 DIRECTIONAL SIGNAGE INDICATING THE ROUTE TO THE PUBLIC
 FACILITIES SHALL BE POSTED IN ACCORDANCE WITH SECTION
 3107 OF THE FLORIDA BUILDING CODE, BUILDING. SUCH
 SIGNAGE SHALL BE LOCATED IN A CORRIDOR OR AISLE, AT THE
 ENTRANCE TO THE FACILITIES FOR CUSTOMERS AND VISITORS.
  