| Plan Review Notes For Permit 13100749 |
| Permit Number |
13100749 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-12-05 11:57:37 | ***PROVISO*** | | | | | | 1. WATER HEATER T&P SHALL BE INSTALLED PER P504.6(1- | | | 13) AND PAN DRAIN SHALL BE INSTALLED PER 504.7.2 | | | | | | 2. IN THE ORIGINAL CONFIGURATION THE COMMON AREA TOILET | | | FACILITIES WOULD BE OVER 500' FROM THE STORE ENTRANCE. | | | P403.3.2 LOCATION OF TOILET FACILITIES IN OCCUPANCIES | | | OTHER THAN COVERED MALLS. | | | ALSO, THE ROUTE TO THE STORE FACILITIES IS THROUGH A | | | STORAGE (STOCK) AREA. | | | P403.3.1 ACCESS. IF THE MALL COMMON RESTROOMS ARE TO BE | | | ACCESSED THROUGH THE EXIT CORRIDOR, PUBLIC ACCESS WILL | | | BE REQUIRED AT ALL TIMES THAT THE BUILDING IS OCCUPIED. | | | | | | 3. MALL DIRECTIONAL SIGNAGE WILL BE REQUIRED: | | | 403.4.1 DIRECTIONAL SIGNAGE. | | | DIRECTIONAL SIGNAGE INDICATING THE ROUTE TO THE PUBLIC | | | FACILITIES SHALL BE POSTED IN ACCORDANCE WITH SECTION | | | 3107 OF THE FLORIDA BUILDING CODE, BUILDING. SUCH | | | SIGNAGE SHALL BE LOCATED IN A CORRIDOR OR AISLE, AT THE | | | ENTRANCE TO THE FACILITIES FOR CUSTOMERS AND VISITORS. | | | |
|