| 2013-12-14 11:42:37 | PASS PROVISO | | | 1) PROVIDE A ENGINEER DETAIL ON HOW THE CONDENSER IS | | | ANCHORED TO | | | THE ROOF PER SECTION 301.12 WIND RESISTANCE 2010 FBC | | | (M) | | | AT FIRST INSPECTION. | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 | | 2013-12-12 08:18:35 | RETURNED FILE TO BIN C34 |
|