| 2013-11-27 06:52:20 | 854 CONNISTON | | | PERMIT #13100620 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | PROVIDE FIRE HYDRANT FLOW TEST INFORMATION. A HYDRANT | | | SHALL BE LOCATED WITHIN 150 FEET OF THE FIRE DEPARTMENT | | | CONNECTION. A PRIVATE FIRE HYDRANT MAY NEED TO BE ADDED | | | ON SITE TO ACCOMODATE THE FDC. | | | PROVIDE CEILING HEIGHT AT PEAK OF ASSEMBLY AREA. | | | INCREASE AREA USED IN HYDRAULIC CALCULATIONS BY 30% AS | | | THE CEILING SLOPE EXCEEDS A PITCH OF 1 AND 6. | | | HYDRAULIC CALCULATIONS SUBMITTED USE K FACTOR OF 5.6. | | | ACTUAL K FACTOR APPEARS TO BE 4.2 THEREFORE MAKING THE | | | PRESSURE INSUFFICIENT. | | | PROVIDE CHAIN WITH LOCK AND TAMPER SWITCHES FOR | | | SUPERVISING THE BACKFLOW PREVENTER IN THE OPEN | | | POSITION. | | | PROVIDE LOCKING KNOX CAPS ON FIRE DEPARTMENT | | | CONNECTION. | | | | | | | | | LAUREN PHILMORE | | | FIRE INSPECTOR II / INVESTIGATOR I | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 804-4783 | | | |
|