| 2013-11-18 17:42:09 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | IT APPEARS ENGINEER IS ELECTING TO USE FBC 2010 | | | EXISTING BUILDING 303.1, PRESCRIPTIVE COMPLIANCE | | | METHODS). | | | | | | THEREFORE, ALL COMMENTS WILL REFER TO FBC 2010 PER FBC | | | 2010 EXISTING BUILDING, ALTERATIONS SHALL COMPLY WITH | | | THE REQUIREMENTS OF THE FLORIDA BUILDING CODE, | | | BUILDING. | | | | | | SEE FBC 704.3 REGARDING PROTECTION OF THE PRIMARY | | | STRUCTURAL FRAME OTHER THAN COLUMNS. ENCASEMENT IS | | | REQUIRED, PLEASE NOTE EXCEPTION. IF USING THE | | | EXCEPTION, NOTE ON THE PLAN. | | | | | | EVEN WITH THE EXCEPTION, THE PROPOSED ALTERATION DOES | | | NOT MAINTAIN ENCASEMENT AS THE PROPOSED ALTERATION | | | PENETRATES THE FIRE RATED ASSEMBLY. ADDITIONALLY, THE | | | PROPOSED ALTERATION IS NOT CONSISTENT WITH THE UL | | | ASSEMBLY REFERENCED. NOTE THAT ENCASEMENT OF STRUCTURAL | | | MEMBERS IN FBC 704 DOES NOT INCLUDE PROVISIONS FOR | | | PENETRATIONS (UNLIKE FIRE WALLS, FIRE BARRIERS, FIRE | | | PARTITIONS). | | | | | | PLEASE FEEL FREE TO CONTACT ME TO DISCUSS. | | | | | | | | | |
|