| Plan Review Notes For Permit 13100605 |
| Permit Number |
13100605 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-10-19 08:36:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. THIS BUILDING WAS CONSTRUCTED AS A FBC 2004 TYPE VA | | | WHICH REQUIRES 1 HOUR FOR ROOF FRAMING. IT IS LIKELY | | | THAT THE CEILING DRYWALL NOTED ON SK-02 "A" IS A PART | | | OF THE RATED ASSEMBLY. | | | | | | SEE FBC 704 AND REVISE PLAN TO SHOW COMPLIANCE. IF | | | EXCEPTIONS ARE USED, PLEASE NOTE ON PLAN. SEE ALSO FBC | | | 2010 EXISTING BUILDING 503. | | | | | | AN ATTEMPT WAS MADE TO LOCATE THE FIRE RATED ASSEMBLY | | | FOR THIS AREA; HOWEVER, DUE TO PLAN SIZE, I WAS UNABLE | | | TO LOCATE QUICKLY. IF YOU WISH TO OBTAIN A SET OF | | | PLANS, PLEASE SUBMIT A RECORDS RESEARCH REQUEST TO | | | [email protected] OR [email protected] | | | | | | 2. REVISE PLAN TO INCLUDE COMPLIANCE METHOD FOR | | | ALTERATION, SEE FBC 2010 EXISTING BUILDING 101.5. | | | COMPLIANCE METHOD NOT CLEAR SO CODES REFERENCED MAY NOT | | | BE CORRECT. |
|