| Plan Review Notes For Permit 13100594 |
| Permit Number |
13100594 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2014-03-27 19:28:43 | IN AN ATTEMPT TO GET THIS APPROVED, I IMPOSED THE | | | FOLLOWING CONDITIONS ON THE PLANS: | | | AS PER NEC 300.5(B), THE INTERIOR OF AN UNDERGROUND | | | RACEWAY SHALL BE CONSIDERED A WET LOCATION; YOUR | | | FEEDERS SHALL BE SO LISTED. | | | THE RISER DIAGRAM DOES NOT REFLECT THE REQUIRED | | | GROUNDING AS PER NEC 250.24 FOR THE NEW DISCONNECT. | | | AS PER NEC 422.52, ELECTRIC WATER COOLERS SHALL BE GFI | | | PROTECTED | | | AS PER NEC 300.5(B), THE INTERIOR OF AN UNDERGROUND | | | RACEWAY SHALL BE CONSIDERED A WET LOCATION; YOUR | | | FEEDERS SHALL BE SO LISTED. | | | THE RISER DIAGRAM DOES NOT REFLECT THE REQUIRED | | | GROUNDING AS PER NEC 250.24 FOR THE NEW DISCONNECT. | | | AS PER NEC 422.52, ELECTRIC WATER COOLERS SHALL BE GFI | | | PROTECTED | | | |
|