2014-03-27 19:28:43IN AN ATTEMPT TO GET THIS APPROVED, I IMPOSED THE
 FOLLOWING CONDITIONS ON THE PLANS:
 AS PER NEC 300.5(B), THE INTERIOR OF AN UNDERGROUND
 RACEWAY SHALL BE CONSIDERED A WET LOCATION; YOUR
 FEEDERS SHALL BE SO LISTED.
 THE RISER DIAGRAM DOES NOT REFLECT THE REQUIRED
 GROUNDING AS PER NEC 250.24 FOR THE NEW DISCONNECT.
 AS PER NEC 422.52, ELECTRIC WATER COOLERS SHALL BE GFI
 PROTECTED
 AS PER NEC 300.5(B), THE INTERIOR OF AN UNDERGROUND
 RACEWAY SHALL BE CONSIDERED A WET LOCATION; YOUR
 FEEDERS SHALL BE SO LISTED.
 THE RISER DIAGRAM DOES NOT REFLECT THE REQUIRED
 GROUNDING AS PER NEC 250.24 FOR THE NEW DISCONNECT.
 AS PER NEC 422.52, ELECTRIC WATER COOLERS SHALL BE GFI
 PROTECTED
  