| Plan Review Notes For Permit 13100594 |
| Permit Number |
13100594 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-11-06 17:54:14 | THE FOLLOWING ITEMS NEED CORRECTIONS: | | | 1. THE EXISTING FEEDER SERVING THE KITCHEN PANEL & LP1 | | | IS 4/0 AL WHICH IS ONLY GOOD FOR 136 AMP WITHOUT TAKING | | | INTO ACCOUNT ANY POSSIBLE VOLTAGE DROP DUE TO DISTANCE | | | NOT INDICATED. | | | 2. PROVIDE LOAD CALC FOR THE KITCHEN PANEL AND ADD THEM | | | TO THE PROVIDED LOAD CALC FOR LP1. | | | 3. FBC-ENERGY CONSERVATION HAS SPECIFIC REQUIREMENTS | | | WHICH ARE NOT INCLUDED ON THE SUBMITTED DRAWINGS. | | | $. SUBMIT A FULL RISER DIAGRAM FOR THE FIRE ALARM ALONG | | | WITH THE STANDBY BATTERY CALCS. | | | | | | RETURNED TO BIN FOR FURTHER REVIEWS |
|