Plan Review Notes
Plan Review Notes For Permit 13100584
Permit Number 13100584
Review Stop B
Sequence Number 1
Notes
Date Text
2013-10-25 18:39:54WINDOW REPLACEMENT, BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC
  
 1- ACCORDING TO FBC-2010 SEC. 1609.4.3 THIS BUILDING IS
 LOCATED IN EXPOSURE "D" NOT EXPOSURE "C". NEED TO
 REVISE ENGINEER CALCULATIONS AS REQUIRED.
  
 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR THE WINDOW MULLIONS. AND, CLEARLY
 SPECIFY THE WINDOW SIZE TO VERIFY COMPLIANCE WITH THE
 ENGINEERED DESIGN PRESSURES. SEC. 1609 FBC.
 ***NOTE: THERE WERE 4 NOA'S SUBMITTTED FOR THE SINGLE
 HUNG WINDOWS AND NONE FOR THE WINDOW MULLIONS.
  
 3- WINDOW NOA 08-1210.02 SUBMITTED FOR THE WINDOWS WAS
 SUPERSEDED BY MIAMI-DADE. VISIT THE MIAMI-DADE WEBSITE
 AND DOWNLOAD CURRENT NOA. DCA RULE 9N-3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712