| Plan Review Notes For Permit 13100584 |
| Permit Number |
13100584 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-10-25 18:39:54 | WINDOW REPLACEMENT, BUILDING REVIEW COMMENTS. | | | CODE: 2010 FBC | | | | | | 1- ACCORDING TO FBC-2010 SEC. 1609.4.3 THIS BUILDING IS | | | LOCATED IN EXPOSURE "D" NOT EXPOSURE "C". NEED TO | | | REVISE ENGINEER CALCULATIONS AS REQUIRED. | | | | | | 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY | | | DCA RULE 9N-3 FOR THE WINDOW MULLIONS. AND, CLEARLY | | | SPECIFY THE WINDOW SIZE TO VERIFY COMPLIANCE WITH THE | | | ENGINEERED DESIGN PRESSURES. SEC. 1609 FBC. | | | ***NOTE: THERE WERE 4 NOA'S SUBMITTTED FOR THE SINGLE | | | HUNG WINDOWS AND NONE FOR THE WINDOW MULLIONS. | | | | | | 3- WINDOW NOA 08-1210.02 SUBMITTED FOR THE WINDOWS WAS | | | SUPERSEDED BY MIAMI-DADE. VISIT THE MIAMI-DADE WEBSITE | | | AND DOWNLOAD CURRENT NOA. DCA RULE 9N-3. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 |
|