| Plan Review Notes For Permit 13100575 |
| Permit Number |
13100575 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-11-07 11:57:39 | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | FBC 107.3.5.3 ? PROVIDE A SITE PLAN TO DEMONSTRATE | | | SETBACKS AND BUILDING SEPARATION. INCLUDE THE USE OF | | | THE OTHER BUILDING ON THE PROPERTY. | | | FBC 107.3.5.3 ? PROVIDE A FLOOR PLAN OF THE SECOND | | | FLOOR AND INDICATE THE USE OF THAT SPACE. RECORDS | | | APPEAR TO INDICATE THE SECOND FLOOR SPACE IS AN | | | EXISTING DWELLING UNIT. IS IT THE INTENT OF THIS | | | APPLICATION FOR IMPROVEMENT TO CONVERT THE EXISTING | | | BUILDING INTO A TWO DWELLING BUILDING? IF SO, YOU MUST | | | COMPLY WITH THE REQUIREMENTS FOR FIRE SEPARATION PER | | | FBC R 302.3 1-HR . THE SUMBITTED PLAN AND PROPERTY | | | APPRAISER RECORDS APPEAR TO INDICATE THE EXISTING SPACE | | | PROPROSED FOR IMPROVEMENT IS A STORAGE AREA. IN THAT | | | CASE, THE DESIGN PARAMETERS MUST CONSIDER FBC-E CHAPTER | | | 9 CHANGE OF OCCUPANCY. FBC 107.3.5.3 ? PROVIDE AN | | | ENERGY SUBMITTAL. THIS REVIEW IS INCOMPLETE PENDING | | | FURTHER CLARIFICATION OF THE INTENT OF THE APPLICATION. |
|