| Plan Review Notes For Permit 13100501 |
| Permit Number |
13100501 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-10-23 15:27:08 | PERMIT #13100501 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | SHEET B1: PLEASE PROVIDE TYPES AND QUANTITIES OF | | | FLAMMABLE LIQUIDS TO BE STORED. | | | | | | SHEETS B2 & B3: PER NFPA 33, CHAPTER 5: 5.1.4 IF WALLS | | | OR CEILING ASSEMBLIES ARE CONSTRUCTED OF SHEET METAL, | | | SINGLE-SKIN ASSEMBLIES SHALL BE NO THINNER THAN 1.2 MM | | | (0.0478 IN.), AND EACH SHEET OF DOUBLE-SKIN ASSEMBLIES | | | SHALL BE NO THINNER THAN 0.9 MM (0.0359 IN.). | | | PLEASE INDICATE THE THICKNESS OF THE SINGLE-SKIN WALLS. | | | | | | SUE ELLEN CALDERON | | | FIRE INSPECTOR & INVESTIGATOR | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 804-4751 | | | | | | | | | | | | | | | | | | |
|