| 2013-11-04 15:30:08 | I AM UNCERTAIN FROM THE EXPLANATION IF THIS IS A | | | SELF-CONTAINED/MANUFACTURED UNIT NEEDING ONLY THE | | | SUPPLY CONNECTIONS OR IT THIS IS A SITE-BUILT PAINT | | | BOOTH BEING WIRED IN ITS ENTIRETY ON SITE. PLEASE | | | ADVISE IF THIS IS A MANUFACTURED UNIT OR IF SITE-BUILT. | | | REGARDLESS, THE FEEDERS ARE NOT ADEQUATE FOR THE LOAD | | | SERVED. RECALCULATE THE DEMANDS AS PER NEC REQUIREMENTS | | | AND SUBMIT FOR APPROVAL. | | | SENT TO SH DESK |
|