2013-11-04 15:30:08I AM UNCERTAIN FROM THE EXPLANATION IF THIS IS A
 SELF-CONTAINED/MANUFACTURED UNIT NEEDING ONLY THE
 SUPPLY CONNECTIONS OR IT THIS IS A SITE-BUILT PAINT
 BOOTH BEING WIRED IN ITS ENTIRETY ON SITE. PLEASE
 ADVISE IF THIS IS A MANUFACTURED UNIT OR IF SITE-BUILT.
 REGARDLESS, THE FEEDERS ARE NOT ADEQUATE FOR THE LOAD
 SERVED. RECALCULATE THE DEMANDS AS PER NEC REQUIREMENTS
 AND SUBMIT FOR APPROVAL.
 SENT TO SH DESK