2013-10-18 08:13:12BUILDING PLAN REVIEW
 PERMIT: 13100501
 ADD: 2707 OKEECHOBEE BLVD
 CONT: FLORIDA FILTRATION
 TEL: (561) 582-5543
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: OCT. 18/ 2013
 ACTION: DENIED
  
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
  
 1) THE PLANS DO NOT PROVIDE CODE COMPLIANCE FOR 2010
 FBC-B SECTION:
 1A) F] 416.2 SPRAY ROOMS.
 SPRAY ROOMS SHALL BE ENCLOSED WITH NOT LESS THAN 1-HOUR
 FIRE BARRIERS CONSTRUCTED IN ACCORDANCE WITH SECTION
 707 OR HORIZONTAL ASSEMBLIES CONSTRUCTED IN ACCORDANCE
 WITH SECTION 712, OR BOTH. FLOORS SHALL BE WATERPROOFED
 AND DRAINED IN AN APPROVED MANNER.
  
 1B) [F] 416.2.1 SURFACES.
 THE INTERIOR SURFACES OF SPRAY ROOMS SHALL BE SMOOTH
 AND SHALL BE SO CONSTRUCTED TO PERMIT THE FREE PASSAGE
 OF EXHAUST AIR FROM ALL PARTS OF THE INTERIOR AND TO
 FACILITATE WASHING AND CLEANING, AND SHALL BE SO
 DESIGNED TO CONFINE RESIDUES WITHIN THE ROOM. ALUMINUM
 SHALL NOT BE USED.
  
 1C) [F] 416.3 SPRAYING SPACES.
 SPRAYING SPACES SHALL BE VENTILATED WITH AN EXHAUST
 SYSTEM TO PREVENT THE ACCUMULATION OF FLAMMABLE MIST OR
 VAPORS IN ACCORDANCE WITH THE FLORIDA BUILDING CODE,
 MECHANICAL. WHERE SUCH SPACES ARE NOT SEPARATELY
 ENCLOSED, NONCOMBUSTIBLE SPRAY CURTAINS SHALL BE
 PROVIDED TO RESTRICT THE SPREAD OF FLAMMABLE VAPORS.
  
 1D) [F] 416.3.1 SURFACES.
 THE INTERIOR SURFACES OF SPRAYING SPACES SHALL BE
 SMOOTH AND CONTINUOUS WITHOUT EDGES; SHALL BE SO
 CONSTRUCTED TO PERMIT THE FREE PASSAGE OF EXHAUST AIR
 FROM ALL PARTS OF THE INTERIOR AND TO FACILITATE
 WASHING AND CLEANING; AND SHALL BE SO DESIGNED TO
 CONFINE RESIDUES WITHIN THE SPRAYING SPACE. ALUMINUM
 SHALL NOT BE USED.
  
 1E) [F] 416.4 SPRAY BOOTHS.
 SPRAY BOOTHS SHALL BE DESIGNED, CONSTRUCTED AND
 OPERATED IN ACCORDANCE WITH THE FLORIDA FIRE PREVENTION
 CODE.
  
 2) 2010 FBC-B 415.3 FIRE SEPARATION DISTANCE.
 GROUP H OCCUPANCIES SHALL BE LOCATED ON PROPERTY IN
 ACCORDANCE WITH THE OTHER PROVISIONS OF THIS CHAPTER.
 IN GROUPS H-2 AND H-3, NOT LESS THAN 25 PERCENT OF THE
 PERIMETER WALL OF THE OCCUPANCY SHALL BE AN EXTERIOR
 WALL.
  
 EXCEPTIONS:
  
 2.1. LIQUID USE, DISPENSING AND MIXING ROOMS HAVING A
 FLOOR AREA OF NOT MORE THAN 500 SQUARE FEET (46.5 M2)
 NEED NOT BE LOCATED ON THE OUTER PERIMETER OF THE
 BUILDING WHERE THEY ARE IN ACCORDANCE WITH THE FLORIDA
 FIRE PREVENTION CODE AND NFPA 30.
  
 2.2. LIQUID STORAGE ROOMS HAVING A FLOOR AREA OF NOT
 MORE THAN 1,000 SQUARE FEET (93 M2) NEED NOT BE LOCATED
 ON THE OUTER PERIMETER WHERE THEY ARE IN ACCORDANCE
 WITH THE FLORIDA FIRE PREVENTION CODE. AND NFPA 30.
  
 2.3. SPRAY PAINT BOOTHS THAT COMPLY WITH THE FLORIDA
 FIRE PREVENTION CODE NEED NOT BE LOCATED ON THE OUTER
 PERIMETER.
  
 3) SHEET B1 NOTES INDICATE STORAGE OF FLAMMABLE,
 LIQUIDS, PLEASE PORVIDE TYPES OF FLAMMABLE LIQUIDS,
 (1A, 1B AND OR 1C) AND QUANITIES TO BE STORED, AND SHOW
 COMPLIANCE WITH 2010 FBC-B TABLE 307.1(1)
  
 4) SHEET B3 INDICATES THE EXHAUST THROUGH THE ROOF, THE
 PLANS DO NOT INDICATE TYPE OF ROOF FRAMING OR ROOF DECK
 AND IF THERE WILLBE ANY EXTRA FRAMING REQUIRED. PLANS
 ARE ALSO MISSING THE WIND DESIN CRITERIA FOR THE
 EXHAUST DUCT ASSEMBLY.
 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN-
 CHAPTER 6 OF ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
 1609.3 WIND SPEED CONVERSION
 4.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10
  
 4.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10.
  
 4.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10
  
 4.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
  
 4.5) COMPONENTS & CLADDING PRESSURES POSITVE & NEGATIVE
 TABLE 1609.2(2) .
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  