| 2013-11-23 09:09:07 | BUILDING PLAN REVIEW |
| | PERMIT: 13100473 |
| | ADD: 1741 PALM BEACH LAKES BLVD (SHADE CANOPY |
| | STRUCTURES) / BROUGHT IN AS 1801 PBL |
| | CONT: EMJ CORP |
| | TEL: (423)464-1537 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2ND REVIEW |
| | DATE: SAT. NOV. 23/ 2013 |
| | ACTION: DENIED |
| | |
| | THE LISTED ITEMS ARE REQUIRED ON THE PLANS TO CLASSIFY |
| | THE STRUTURE AND OCCUPANCY: |
| | 1) 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION, |
| | 107.3.5.1.1 MINIMUM PLAN REVIEW CRITERIA FOR COMMERCIAL |
| | BUILDINGS; |
| | 1A) MINIMUM BUILDING TYPE: 2010 FBC-B 3102.3 |
| | |
| | 1B) OCCUPANCY TYPE: A-3 ASSEMBLY USESRECREATION OR |
| | OTHER AMUSEMENTAND OR OTHER ASSEMBLY USES NOT |
| | CLASSIFIED ELSEWHERE. |
| | |
| | 2) 2010 FBC-B 3102.3 TYPE OF CONSTRUCTION. |
| | NONCOMBUSTIBLE MEMBRANE STRUCTURES SHALL BE CLASSIFIED |
| | AS TYPE IIB CONSTRUCTION. NONCOMBUSTIBLE FRAME OR |
| | CABLE-SUPPORTED STRUCTURES COVERED BY AN APPROVED |
| | MEMBRANE IN ACCORDANCE WITH SECTION 3102.3.1 SHALL BE |
| | CLASSIFIED AS TYPE IIB CONSTRUCTION. |
| | |
| | FLORIDA BUILDING OFFICIALS ASSOCIATION REPORT 6027 / |
| | 2004 |
| | MAY OR MAY NOT REQUIRE SPRINKLERS IT WILL DEPEND ON |
| | WILL THERE BE KIOSK BE UNDER THE CANOPIES, WILL THERE |
| | BE SEATING WITH COMBUSTIBLE FURNATURE, WILL THERE BE |
| | AUTOMOBILES SHOWED IN UNDER THE VARIOUS KIOSK? |
| | NFPA 13, 8.15.7.5 STATES, "SPRINKLERES SHALL BE |
| | INSTALLED UNDER ROOFS, CANOPIES, OR PORTE-COCHERES OVER |
| | AREAS WHERE COMBUSTIBLES ARE STORED AND HANDLED. ALSO |
| | STATES IN CANOPIES UNDER WHICH MEALS ARE SERVED OR |
| | PEOPLE ARE SEATED, THE FURNIISHINGS MAY BE COMBUSTIBLE. |
| | ANY OF THE FORE GOING COULD TRIGGER THE REQUIREMENT FOR |
| | FIRE SPRINKLERS. |
| | |
| | 3) COMPLIED. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |