| Plan Review Notes For Permit 13100452 |
| Permit Number |
13100452 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-10-28 17:38:45 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2010 | | | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL | | | | | | 1. DESIGN PROFESSIONAL FOR THE RENOVATION SPECIFIES | | | BUILDING DESIGN PRESSURE AS 170; NOT CLEAR WHETHER THIS | | | APPLIES TO SIGNAGE. SIGN ENGINEERING TO BE REVIEWED BY | | | DESIGNER OF RECORD, FBC 1609, OR PROVIDE CLARIFICATION | | | LETTER FROM HARTLEY PURDY ARCHITCTURE, OR REVISE | | | ENGINEERING DESIGN TO 170MPH EXPOSURE C MINIMUM. | | | | | | 2. PROPOSED FASTENING NOT CLEAR. THE SECTION ON THE | | | LEFT SIDE OF THE PLAN SHOWS (5) 1/4" X 2" TPACONS; 5 | | | DOES NOT APPEAR TO BE ENOUGH FASTENERS FOR A 42" X 48" | | | M-ARCH SIGN. INSTALL INSTRUCTIONS STATE LAG SCREWS AND | | | WASHERS WILL BE USED FOR INSTALLATION; NOT CLEAR FOR | | | WHICH OF THE SIGNS THIS APPLIES AND MINIMUM NUMBER OF | | | FASTENERS NOT SPECIFIED. | | | | | | 3. PROVIDE A VERIFIABLE CONTRACT FOR THIS JOB. VALUE IS | | | TO INCLUDE LABOR, MATERIALS, AND ENGINEERING, EVEN IF | | | THE MATERIALS ARE SUPPLIED BY OTHERS, FBC 109. | | | | | | | | | |
|