| 2013-12-18 16:07:51 | RESIDENTIAL (R3) ADDITION, SECOND BUILDING REVIEW |
| | COMMENTS. |
| | CODE: 2010 FBC. |
| | |
| | 1- PROVIDE ENERGY CALCULATIONS. SEC. 101.4.3 OF 2010 |
| | FBC-ENERGY CONSERVATION. |
| | (REPEAT COMMENT. NOT ADDRESSED). |
| | ***NOTE: PLEASE MAKE SURE FORM IS FILLED COMPLETELY, |
| | INCLUDING THE INFORMATION ON TOP OF FORM AND IS |
| | CERTIFIED AND DATED BY ALL THE PARTIES AT BOTTOM OF |
| | FORM. |
| | |
| | 2- PROVIDE COMPLETE DRAWINGS SHOWING FRAMING DETAILS |
| | AND SPECIFICATIONS SHOWING COMPLIANCE WITH SEC. R301 OF |
| | 2010 FBC-RESIDENTIAL. |
| | |
| | *(A) DRAWINGS SUBMITTED DON'T SPECIFY STRUCTURAL BUCK |
| | ATTACHMENT. REVISE AS REQUIRED. |
| | **(B) NEW DOOR JAMB, SILL AND HEADER DETAILS SUBMITTED |
| | ARE FOR WINDOWS NOT FOR SLIDING GLASS DOORS. REVISE AS |
| | REQUIRED. |
| | ***(C) STRUCTURAL BUCK NEED TO PROVIDE FULL SUPPORT TO |
| | THE SLIDING GLASS DOOR FRAME AS REQUIRED BY SEC. |
| | R612.10.2.1 OF 2010 FBC-RESIDENTIAL. REVISE DETAILS AS |
| | REQUIRED. |
| | |
| | 3- VALUE DECLARED IN THE PERMIT APPLICATION IS TOO LOW. |
| | REVISE VALUE TO INCLUDE ALL THE LABOR, MATERIALS, |
| | OVERHEAD AND PROFIT AND DESIGN PROFESSIONAL FEES. SEC. |
| | 109.3 CITY AMENDMENTS TO FBC. |
| | (REPEAT COMMENT. NOT ADDRESSED). |
| | |
| | 4- MASTER BEDROOM: THERE WAS AN SLIDING GLASS DOOR |
| | LEADING OUT TO THE PORCH. THE EGRESS FROM THE MASTER |
| | BEDROOM IS AFFECTED. SPECIFY THE TYPE AND SIZE OF |
| | EXISTING WINDOW TO VERIFY IF THIS WINDOW WILL COMPLY |
| | WITH THE EGRESS REQUIREMENTS. SEC. 601.2 OF 2010 |
| | FBC-EXISTING BUILDING. |
| | |
| | *(A) DRAWINGS SUBMITTED DON'T SHOW SIZE OF HORIZONTAL |
| | SLIDER WINDOW. |
| | **(B) DRAWINGS SUBMITTED SHOW WINDOWS ON THE NORTH WEST |
| | WALL. (NORTH ARROW ON KEY MAP SUBMITTED NEED TO BE |
| | REVISED TO MATCH ACTUAL BUILDING ORIENTATION. SEE |
| | AERIAL MAP ON PROPERTY APPRAISAL RECORDS). THIS WALL IS |
| | ON THE ZERO LOT LINE AND OPENINGS ARE NOT ALLOWED. |
| | REVISE DRAWINGS AS REQUIRED. |
| | ***NOTE: ANY OPENINGS ON THE THIS WALL NEED TO BE |
| | ENCLOSED WITH ONE HOUR FIRE RATED ASSEMBLY. (NOTE: |
| | OPENINGS ON THIS WALL WILL BE VERIFIED BY THE |
| | INSPECTOR). |
| | |
| | ****NOTE: PLEASE PROVIDE A RESPONSE LETTER ADDRESSING |
| | EACH COMMENT. THIS WILL EXPEDITE THE REVIEW PROCESS. |
| | |