Plan Review Notes
Plan Review Notes For Permit 13100426
Permit Number 13100426
Review Stop B
Sequence Number 5
Notes
Date Text
2014-09-06 11:44:00****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 COMMENTS FROM PREVIOUS LIST ARE BELOW FOR REFERENCE.
  
 THE LETTER FROM THE BUILDING OWNER IS PENDING REVIEW BY
 THE BUILDING OFFICIAL. MY APOLOGIES FOR THE DELAY.
  
 I WAS UNABLE TO LOCATE THE LETTER FROM THE ENGINEER
 ACKNOWLEDGING THE RESPONSIBILITY OF THE BUILDING OWNER
 TO FOLLOW THESE GUIDELINES AS A CONDITION OF APPROVAL
 OF THE DESIGN (SEE PREVIOUS LIST).
  
 REPONSE LETTER IS FROM THE SURVEYOR. AS SURVEYORS ARE
 NOT LICENSED TO DO DESIGN WORK, OR TO DO INSTALLATIONS,
 PLEASE BE ADVISED THAT I CONSIDER "WHAT IF SCENARIOS"
 DESIGN WORK WHICH SHOULD BE OVERSEEN BY AN ARCHITECT OR
 AN ENGINEER KNOWLEDGEABLE ABOUT LIFE SAFETY AND FLOOD
 LOAD RESISTANCE. IT WOULD BE MORE APPROPRIATE FOR THE
 LICENSED ENGINEER OR THE LICENSED CONTRACTOR TO BE
 DEALING WITH THESE CODE ISSUES. FAILURE TO UTILIZE THE
 PROFESSIONALS WHO ARE LICENSED TO DO THIS TYPE OF
 DESIGN HAS SIGNIFICANTLY DELAYED THIS PROJECT. AT THIS
 POINT I CONSIDER THE CODE ISSUES ALMOST RESOLVED. FOR
 FUTURE COMMERCIAL PROJECTS, PLEASE HAVE A KNOWLEDGEABLE
 DESIGN PROFESSIONAL INVOLVED FROM THE BEGINNING TO
 AVOID RISK TO THE OCCUPANTS.
  
 RESPONSE LETTER STATES THAT THE PRODUCT HAS BEEN
 TESTED. THIS IS NOT THE CASE, BUT THIS ISSUE WILL BE
 RESOLVED UPON APPROVAL OF THE INSPECTION LETTER. THE
 MANUFACTURER UNDERSTANDS THE ISSUES AND HAS NOT ONLY
 AGREED THAT THE REQUIREMENT IS APPROPRIATE, BUT IS
 CONSIDERING SUGGESTING THIS FOR OTHER JOBS WITH A
 SIMILAR INSTALLATION.
  
  
 1. SEE THE UL LISTING FOR THE FIRE CURTAIN. THIS WAS
 DESIGNED TO BE INSTALLED IN AN AIR DUCT, NOT AN
 EXTERIOR WALL.
  
 THE MANUFACTURER OF THE FIRE CURTAIN HAS STATED THAT
 THEY CANNOT PROVIDE ANY ASSURANCE THAT THE FIRE CURTAIN
 WOULD OPERATE AFTER EXPOSURE TO THE ELEMENTS OR A FLOOD
 EVENT.
  
 THEREFORE, THE PROPOSED APPLICATION DOES NOT COMPLY
 WITH FBC CHAPTER 7. HOWEVER, PER BUILDING OFFICIAL,
 THIS APPLICATION WILL BE APPROVED UNDER ALTERNATIVE
 MATERIALS AND METHODS 104.11 UNDER THE FOLLOWING
 CONDITIONS:
  
 THE FIRE CURTAINS WILL BE INSPECTED AND TESTED BY A
 DBPR LICENSED PROFESSIONAL UNDER THE FOLLOWING
 CONDITIONS:
  
 ANNUALLY
 AFTER A FIRE EVENT
 AFTER A FLOOD EVENT
  
 THE BUILDING OWNER SHALL PROVIDE A LETTER OF COMMITMENT
 STATING SUCH. THIS REQUIREMENT WILL REMAIN IN EFFECT AS
 LONG AS THE VENTS AND FIRE CURTAINS ARE INSTALLED IN
 THE FIRE RATED WALLS AND REMAINS THE RESPONSIBILITY OF
 THE BUILDING MANAGEMENT AND BUILDING OWNERS. THIS
 LETTER IS TO BE FILED WITH THE PALM BEACH COUNTY
 CLERK'S OFFICE.
  
 THE ENGINEER IS TO WRITE A LETTER ACKNOWLEDGING THE
 RESPONSIBILITY OF THE BUILDING OWNER TO FOLLOW THESE
 GUIDELINES AS A CONDITION OF APPROVAL OF THE DESIGN.
  
  