| 2014-08-01 16:23:32 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. SEE THE UL LISTING FOR THE FIRE CURTAIN. THIS WAS | | | DESIGNED TO BE INSTALLED IN AN AIR DUCT, NOT AN | | | EXTERIOR WALL. | | | | | | THE MANUFACTURER OF THE FIRE CURTAIN HAS STATED THAT | | | THEY CANNOT PROVIDE ANY ASSURANCE THAT THE FIRE CURTAIN | | | WOULD OPERATE AFTER EXPOSURE TO THE ELEMENTS OR A FLOOD | | | EVENT. | | | | | | THEREFORE, THE PROPOSED APPLICATION DOES NOT COMPLY | | | WITH FBC CHAPTER 7. HOWEVER, PER BUILDING OFFICIAL, | | | THIS APPLICATION WILL BE APPROVED UNDER ALTERNATIVE | | | MATERIALS AND METHODS 104.11 UNDER THE FOLLOWING | | | CONDITIONS: | | | | | | THE FIRE CURTAINS WILL BE INSPECTED AND TESTED BY A | | | DBPR LICENSED PROFESSIONAL UNDER THE FOLLOWING | | | CONDITIONS: | | | | | | ANNUALLY | | | AFTER A FIRE EVENT | | | AFTER A FLOOD EVENT | | | | | | THE BUILDING OWNER SHALL PROVIDE A LETTER OF COMMITMENT | | | STATING SUCH. THIS REQUIREMENT WILL REMAIN IN EFFECT AS | | | LONG AS THE VENTS AND FIRE CURTAINS ARE INSTALLED IN | | | THE FIRE RATED WALLS AND REMAINS THE RESPONSIBILITY OF | | | THE BUILDING MANAGEMENT AND BUILDING OWNERS. THIS | | | LETTER IS TO BE FILED WITH THE PALM BEACH COUNTY | | | CLERK'S OFFICE. | | | | | | THE ENGINEER IS TO WRITE A LETTER ACKNOWLEDGING THE | | | RESPONSIBILITY OF THE BUILDING OWNER TO FOLLOW THESE | | | GUIDELINES AS A CONDITION OF APPROVAL OF THE DESIGN. | | | | | | |
|