Plan Review Notes
Plan Review Notes For Permit 13100426
Permit Number 13100426
Review Stop B
Sequence Number 4
Notes
Date Text
2014-08-01 16:23:32****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. SEE THE UL LISTING FOR THE FIRE CURTAIN. THIS WAS
 DESIGNED TO BE INSTALLED IN AN AIR DUCT, NOT AN
 EXTERIOR WALL.
  
 THE MANUFACTURER OF THE FIRE CURTAIN HAS STATED THAT
 THEY CANNOT PROVIDE ANY ASSURANCE THAT THE FIRE CURTAIN
 WOULD OPERATE AFTER EXPOSURE TO THE ELEMENTS OR A FLOOD
 EVENT.
  
 THEREFORE, THE PROPOSED APPLICATION DOES NOT COMPLY
 WITH FBC CHAPTER 7. HOWEVER, PER BUILDING OFFICIAL,
 THIS APPLICATION WILL BE APPROVED UNDER ALTERNATIVE
 MATERIALS AND METHODS 104.11 UNDER THE FOLLOWING
 CONDITIONS:
  
 THE FIRE CURTAINS WILL BE INSPECTED AND TESTED BY A
 DBPR LICENSED PROFESSIONAL UNDER THE FOLLOWING
 CONDITIONS:
  
 ANNUALLY
 AFTER A FIRE EVENT
 AFTER A FLOOD EVENT
  
 THE BUILDING OWNER SHALL PROVIDE A LETTER OF COMMITMENT
 STATING SUCH. THIS REQUIREMENT WILL REMAIN IN EFFECT AS
 LONG AS THE VENTS AND FIRE CURTAINS ARE INSTALLED IN
 THE FIRE RATED WALLS AND REMAINS THE RESPONSIBILITY OF
 THE BUILDING MANAGEMENT AND BUILDING OWNERS. THIS
 LETTER IS TO BE FILED WITH THE PALM BEACH COUNTY
 CLERK'S OFFICE.
  
 THE ENGINEER IS TO WRITE A LETTER ACKNOWLEDGING THE
 RESPONSIBILITY OF THE BUILDING OWNER TO FOLLOW THESE
 GUIDELINES AS A CONDITION OF APPROVAL OF THE DESIGN.
  
  