 REVIEW COMMENTS - FIRE DEPARTMENT
  
 EXPLAIN THE RATIONALE FOR PLACING A FLOOD VENT BETWEEN
 THE ELEVATOR SHAFT AND ADJACENT TRASH ROOM. A FIRE IN
 THE TRASH ROOM COULD RESULT IN SMOKE TRANSFER TO THE
 ELEVATOR SHAFT AND OTHER FLOORS ABOVE. FIRE HISTORY
 CONFIRMS SMOKE IN ELEVATOR HOISTWAYS HAS PROVEN TO BE
 DEADLY . THIS DESIGN HAS SERIOUS LIFE SAFETY
 IMPLICATIONS. ARE THE PROJECT ENGINEERS ACCEPTING
 RESPONSIBILITY FOR THE LIFE SAFETY DESIGN OF THE
 BUILDING?
  
 THE PLANS INDICATE FIRE DAMPERS ARE TO BE INSTALLED
 WITH THE FLOOD VENTS. HAVE THESE PRODUCTS BEEN TESTED
 AND LISTED TO BE USED TOGETHER?
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL