| Plan Review Notes For Permit 13100426 |
| Permit Number |
13100426 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2013-12-14 09:42:01 | 5600 NORTH FLAGLER DRIVE | | | PERMIT #13100426 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | EXPLAIN THE RATIONALE FOR PLACING A FLOOD VENT BETWEEN | | | THE ELEVATOR SHAFT AND ADJACENT TRASH ROOM. A FIRE IN | | | THE TRASH ROOM COULD RESULT IN SMOKE TRANSFER TO THE | | | ELEVATOR SHAFT AND OTHER FLOORS ABOVE. FIRE HISTORY | | | CONFIRMS SMOKE IN ELEVATOR HOISTWAYS HAS PROVEN TO BE | | | DEADLY . THIS DESIGN HAS SERIOUS LIFE SAFETY | | | IMPLICATIONS. ARE THE PROJECT ENGINEERS ACCEPTING | | | RESPONSIBILITY FOR THE LIFE SAFETY DESIGN OF THE | | | BUILDING? | | | | | | THE PLANS INDICATE FIRE DAMPERS ARE TO BE INSTALLED | | | WITH THE FLOOD VENTS. HAVE THESE PRODUCTS BEEN TESTED | | | AND LISTED TO BE USED TOGETHER? | | | | | | WESLEY JOLIN | | | FIRE INVESTIGATOR & INSPECTOR | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 805-6730 |
|