 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SEVERAL OF THE VENT LOCATIONS APPEAR TO BE LOCATED IN
 FIRE-RESISTANT RATED WALLS OF STAIR TOWERS, STORAGE
 ROOMS AND TRASH ROOMS ETC. UNPROTECTED OR NON-FIRE
 RATED OPENINGS AND PENETRATIONS ARE NOT PERMITTED BY
 THE FIRE AND LIFE SAFETY CODES AS THIS WILL ALLOW
 PASSAGE OF HEAT AND SMOKE.
  
 PER NFPA 101 SECTION 7.1.3.2.1, PENETRATIONS INTO, AND
 OPENINGS THROUGH, AN EXIT ENCLOSURE ASSEMBLY SHALL BE
 LIMITED TO DOOR ASSEMBLIES FROM NORMALLY OCCUPIED
 SPACES AND CORRIDORS, REQUIRED EXIT DOOR OPENINGS,
 ELECTRICAL CONDUIT SERVING THE EXIT ENCLOSURE, DUCTWORK
 AND EQUIPMENT NECESSARY FOR INDEPENDENT STAIR
 PRESSURIZATION, WATER OR STEAM PIPING NECESSARY FOR THE
 HEATING OR COOLING OF THE EXIT ENCLOSURE, SPRINKLER
 PIPING, STANDPIPES, AND PENETRATIONS FOR FIRE ALARM
 CIRCUITS, WHERE THE CIRCUITS ARE INSTALLED IN METAL
 CONDUIT AND THE PENETRATIONS ARE PROTECTED.
  