| 2013-10-22 18:03:14 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | **NO PLAN SUBMITTED - A PLAN PREPARED BY A DESIGN |
| | PROFEESIONAL IS REQUIRED, FS471/FS481. PLAN IS TO SHOW |
| | THE LOCATION OF PROPOSED WORK AS WELL AS ADDRESS THE |
| | FOLLOWING ISSUES** |
| | |
| | **PLEASE SEE ITEM #11 AND CONTACT ME IMMEDIATELY TO |
| | ADVISE AS TO HOW THE LIFE SAFETY ISSUE WILL BE |
| | RESOLVED** |
| | |
| | 1. APPLICATION IS FOR 16 FLOOD VENTS, ELEVATION |
| | CERTIFICATE A8B STATES THAT THERE ARE 21. PLEASE |
| | CORRELATE FBC 107. |
| | |
| | 2. SEE PAGE 1 OF 2 OF THE ICC EVALUATION REPORT. ITEM |
| | 2.0 STATES THAT THIS IS TO BE USED ON NON FIRE |
| | RESISTANT WALLS. ON THE PLAN, INCLUDE BUILDING TYPE FBC |
| | CHAPTER 6 AS WELL AS ANY EXISTING RATED WALLS, FBC |
| | CHAPTER 7. NOTE THAT VENTS APPEAR TO BE SHOWN IN THE |
| | STAIR AND ELEVATOR SHAFTS. |
| | |
| | 3. ON THE PLAN, INDICATE METHOD OF COMPLIANCE FOR THIS |
| | EXISTING BUILDING, SEE FBC 2010 EXISTING BUILDING |
| | 101.5. NOT ENOUGH INFORMATION HAS BEEN PROVIDED TO |
| | DETERMINE CODE COMPLIANCE OR TO PROVIDE A COMPLETE |
| | CHECKLIST. |
| | |
| | 4. INCLUDE WIND DESIGN CRITERIA FBC 1603.1.4 AND FLOOD |
| | DESIGN DATA FBC 1603.1.7, SEE ALSO FBC 1612.5. IT IS |
| | NOT CLEAR WHETHER THIS BUILDING HAS REACHED THE |
| | SUBSTANTIAL IMPROVEMENT THRESHOLD (LIFETIME CUMULATIVE |
| | IMPROVEMENTS) BUT IT APPEARS THAT PROPERTY OWNER IS |
| | ATTEMPTING TO COMPLY WITH NFIP GUIDELINES. |
| | |
| | 5. VALUE IS TOO LOW. VALUE IS TO INCLUDE ENGINEERING, |
| | MATERIALS, LABOR, OVERHEAD, PROFIT, SEE FBC 109. |
| | |
| | 6. SEE ELEVATION CERTIFICATE INSTRUCTIONS, ITEM A5, IF |
| | LAT/LONG COORDINATES ARE PROVIDED BY A SURVEYOR, |
| | INDICATE THE METHOD USED TO DETERMINE THE |
| | LATITUDE/LONGITUDE IN THE COMMENTS AREA OF SECTION D, |
| | PLEASE REVISE. |
| | |
| | 7. SEE ELEVATION CERTIFICATE, ITEM A8 (C). PLEASE |
| | PROVIDE CALCULATIONS AS TO HOW IT HAS BEEN DETERMINED |
| | THAT THERE ARE 4200 SQUARE INCHES OF NET AREA. THE |
| | LOCATION PLAN SHOWS FIVE DOUBLE VENTS, 152 SI EACH, AND |
| | ELEVEN SINGLE VENTS, 76 SI EACH. |
| | |
| | ALSO PROVIDE INFORMATION AS TO THE CALCULATIONS FOR |
| | EACH AREA WERE DETERMINED. FOR INSTANCE, MAINTENANCE & |
| | BUILDING STORAGE IS SHOWN AS 800 SF/1000 WITH TWO |
| | DOUBLE VENTS. |
| | |
| | 8. PLAN TO INCLUDE THE MODEL NUMBER OF THE VENTS |
| | PROPOSED. THE PRODUCT APPROVAL SUBMITTED INCLUDES SIX |
| | DIFFERENT MODELS. |
| | |
| | 9. PRODUCT APPROVALS ARE TO BE REVIEWED BY DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL, FBC 107.3.1. |
| | |
| | 10. PHOTOS PROVIDED APPEAR TO SHOW NEW DRYWALL (CORNER |
| | BEAAD VISIBLE IN MORE THAN ONE LOCATION). IT APPEARS |
| | THAT MORE WORK MAY HAVE BEEN PERFORMED OTHER THAN THE |
| | INSTALLATION OF THE FLOOD VENTS. IF THIS IS THE CASE, |
| | INCLUDE THE ADDITIONAL WORK ON THE PLAN. |
| | |
| | 11. IT APPEARS BASED ON THE LOCATION PLAN THAT FLOOD |
| | VENTS WERE INSTALLED BETWEEN THE OWNER STORAGE AND A |
| | STAIR, AND BETWEEN THE STAIR AND ELEVATORS. IS THIS A |
| | REQUIRED EXIT STAIR? PRESSURIZED STAIR? IT APPEARS THAT |
| | A LIFE SAFETY ISSUE MAY HAVE BEEN CREATED. PLEASE |
| | PROVIDE MORE INFORMATION, FBC CHAPTER 10, CHAPTER 7. |
| | |
| | 12. SEE THE ICC EVALUATION REPORT, ITEM 4.0, SMARTVENTS |
| | ARE DESIGNED TO BE INSTALLED INTO WALLS FROM THE |
| | EXTERIOR SIDE. INTERIOR INSTALLATIONS SHOWN, PLEASE |
| | ADDRESS. |
| | |
| | |