| 2013-11-20 11:52:06 | 2010 FBC EXISTING BUILDING |
| | LEVEL 1 ALTERATION |
| | |
| | NOTE: THE PERMIT FOR THIS PROJECT HAS BEEN APPLIED FOR |
| | UNDER THE OWNER BUILDER EXEMPTION OF CHAPTER 489 |
| | CONTRACTING. THESE ONE AND TWO FAMILY RESIDENCES ARE |
| | REQUIRED TO BE FOR THE OCCUPANCY OR USE OF THE OWNER |
| | AND CAN NOT BE OFFERED FOR SALE OR LEASE FOR ONE YEAR |
| | AFTER THE COMPLETION OF THE CONSTRUCTION. |
| | |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) SMOKE ALARMS ARE REQUIRED IN ALL 3 DWELLING UNITS. |
| | R314.3.1 ALTERATIONS, REPAIRS AND ADDITIONS. |
| | WHEN ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A |
| | PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE |
| | ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL |
| | DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS |
| | LOCATED AS REQUIRED FOR NEW DWELLINGS. |
| | |
| | 2) SUBMIT TWO COPIES OF PRODUCT APPROVALS AS REQUIRED |
| | BY DCA RULE 9N-3 FOR THE NEW SLIDING GLASS DOORS AND |
| | STRUCTURAL CONNECTORS. |
| | |
| | 3) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED |
| | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. CITY |
| | AMENDMENTS 107.2.1 |
| | |
| | 4) SPECIFY THE WATER PROOFING SYSTEM (SUBMIT 2 COPIES |
| | OF PRODUCT APPROVALS) THAT WILL BE USED ON THE BALCONY |
| | AND PROVIDE A WALL TO DECK FLASHING DETAIL. CITY |
| | AMENDMENTS 107.2.1 |
| | |
| | 5) THE ELEVATIONS OF THE REAR BUILDING ON SHEET A-6 OF |
| | THE PLANS SHOW A PARTIALLY ENCLOSED PORCH THAT APPEARS |
| | TO BE CANTILEVERED. HAVE THIS CONDITION EVALUATED BY AN |
| | ENGINEER AND SUBMIT A SIGNED AND SEALED LETTER STATING |
| | THAT IT'S CONSTRUCTION WILL SAFELY SUPPORT ALL LIVE |
| | LOADS, DEAD LOADS, FLOOR LOADS, ROOF LOADS AND WIND |
| | LOADS AS REQUIRED BY THE FLORIDA BUILDING CODE. FBC |
| | R301.1 |
| | |
| | 6) CLARIFY THE ATTACHMENT OF THE EXISTING CONCRETE |
| | FOOTING TO THE NEW REINFORCED BLOCK FOUNDATION |
| | EXTENSION WALL SHOWN IN DETAIL 2 ON SHEET S-1. FBC R404 |
| | |
| | 7) THERE IS NO TIE BEAM WITH HORIZONTAL REINFORCEMENT |
| | SHOWN AT THE TOP OF THE 8" BLOCK RETAINING WALL IN |
| | DETAIL 6 ON SHEET S-1. PLEASE CLARIFY. FBC R404 |
| | |
| | 8) THE REPAIRED WALLS AND CEILINGS FORMING THE BUILDING |
| | ENVELOPE SHALL BE INSULATED AND THE REPLACED COMPONENTS |
| | (SUCH AS WATER HEATERS) ARE REQUIRED TO COMPLY WITH |
| | CHAPTER 402 OF THE FLORIDA BUILDING CODE ENERGY |
| | CONSERVATION. |
| | |
| | 9) HOW WILL THE FOUNDATION WALLS AND CONCRETE FLOOR |
| | SLAB BE WATER-PROOFED TO PREVENT THE EXCAVATED AREAS |
| | FROM FILLING WITH WATER. FBC R406.2 |
| | |
| | 10) SHOW COMPLIANCE WITH FBC R408.4 FOR ACCESS TO UNDER |
| | FLOOR SPACE. |
| | |
| | 11) SHOW COMPLIANCE WITH FBC R408.1 FOR UNDER FLOOR |
| | SPACE VENTILATION. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |