| Plan Review Notes For Permit 13100366 |
| Permit Number |
13100366 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-11-06 13:36:13 | THE FOLLOWING ITEMS WERE NOTED AND NEED CORRECTION FOR | | | THE ELECTRICAL PLANS REVIEW. | | | 1. PAGE CVR MAKES REFERENCE TO NEC 2005 RATHER THAN THE | | | 2008 NOW IN EFFECT. | | | 2. THE LIGHTING CONTROL DIAGRAM DOES NOT MEET | | | FBC-ENERGY CONSERVATION. NO OVER RIDE PROVISIONS | | | INDICATED. | | | 3. THOUGH THE RISER DIAGRAMS SHOW THE TRANSFORMER, IT | | | DOES NOT APPEAR ON THE FLOOR PLANS | | | 4. THE ELECTRICAL RISER DIAGRAM SHOWN ON PAGE E@ DOES | | | NOT MATCH THE ON SHOWN ON PAGE E3. | | | | | | PLEASE CORRECT THE ABOVE MENTIONED DEFICIENCIES AND | | | RESUBMIT FOR REVIEW. | | | | | | SENT TO SH DESK |
|