| 2013-10-22 16:30:24 | BUILDING PLAN REVIEW |
| | PERMIT: 13100355 |
| | ADD: 1781 PALM BEACH LAKES # W221 |
| | CONT: TO BE DETERMINED |
| | TEL: |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: OCT. 22/ 2013 |
| | ACTION: PROVISO |
| | |
| | 1) BEFORE PERMIT ISSUANCE: |
| | PB OUTLET MALLS: |
| | A LETTER FROM THE QUALIFIER OF BOTH THE SHELL |
| | CONTRACTOR (EMJ CORPORATION) AND TENANT BUILD-OUT |
| | CONTRACTOR MUST BE PROVIDED BEFORE TENANT BUILD-OUT |
| | PERMIT CAN BE ISSUED, IF THE TENANT BUILD-OUT |
| | CONTRACTOR WISHES TO START WORK BEFORE THE SHELL WORK |
| | HAS RECEIVED A CERTIFICATE OF COMPLETION, AGREEING THEY |
| | WILL WORK TOGETHER TO ACHIEVE CODE COMPLIANCE. THESE |
| | DOCUMENTS WILL NEED TO BE SIGNED BY THE QUALIFIER AND |
| | NOTARIZED. |
| | |
| | 2) SHEET A10.1 THE ACCESSIBLE DRESSING / FITTING ROOM |
| | BENCH IS INDICATED FREESTANDING, PLEASE PROVIDE |
| | COMPLIANCE WITH 2010 FBC- ACCESSIBILITY CODE SECTION |
| | 903.4. |
| | 2010 ACCESSIBILITY CODE 903.4 BACK SUPPORT. |
| | THE BENCH SHALL PROVIDE FOR BACK SUPPORT OR SHALL BE |
| | AFFIXED TO A WALL. BACK SUPPORT SHALL BE 42 INCHES |
| | (1065 MM) LONG MINIMUM AND SHALL EXTEND FROM A POINT 2 |
| | INCHES (51 MM) MAXIMUM ABOVE THE SEAT SURFACE TO A |
| | POINT 18 INCHES (455 MM) MINIMUM ABOVE THE SEAT |
| | SURFACE. BACK SUPPORT SHALL BE 21/2 INCHES (64 MM) |
| | MAXIMUM FROM THE REAR EDGE OF THE SEAT MEASURED |
| | HORIZONTALLY. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |