2013-11-07 14:44:09***PROVISO***
 1. PER ORIGINAL PLANS, THE FUEL GAS IS EXISTING NATURAL
 GAS IN THE CEILING OF EACH FOOD COURT UNIT. THIS IS A
 2LB HYBRID SYSTEM WITH A 2LB TO 1/2 LB REGULATOR IN THE
 CEILING AREA. THE 1 1/2" 1/2LB CONNECTION IS CAPABLE OF
 873,000 BTU FOR 50'.
  
 2. PER FUEL GAS TABLE 402.4(2) 1 1/4" PIPE IS REQUIRED
 TO THE WOK RANGE.
  