| Plan Review Notes For Permit 13100330 |
| Permit Number |
13100330 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-11-07 14:44:09 | ***PROVISO*** | | | 1. PER ORIGINAL PLANS, THE FUEL GAS IS EXISTING NATURAL | | | GAS IN THE CEILING OF EACH FOOD COURT UNIT. THIS IS A | | | 2LB HYBRID SYSTEM WITH A 2LB TO 1/2 LB REGULATOR IN THE | | | CEILING AREA. THE 1 1/2" 1/2LB CONNECTION IS CAPABLE OF | | | 873,000 BTU FOR 50'. | | | | | | 2. PER FUEL GAS TABLE 402.4(2) 1 1/4" PIPE IS REQUIRED | | | TO THE WOK RANGE. | | | |
|