| 2013-10-22 15:50:03 | BUILDING PLAN REVIEW |
| | PERMIT: 13100312 |
| | ADD: 1771 PALM BEACH LAKES # W307 |
| | CONT: TBD |
| | TEL: |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: OCT. 22/ 2013 |
| | ACTION: DENIED |
| | |
| | 1) BEFORE PERMIT ISSUANCE: |
| | PB OUTLET MALLS: |
| | A LETTER FROM THE QUALIFIER OF BOTH THE SHELL |
| | CONTRACTOR (EMJ CORPORATION) AND TENANT BUILD-OUT |
| | CONTRACTOR MUST BE PROVIDED BEFORE TENANT BUILD-OUT |
| | PERMIT CAN BE ISSUED, IF THE TENANT BUILD-OUT |
| | CONTRACTOR WISHES TO START WORK BEFORE THE SHELL WORK |
| | HAS RECEIVED A CERTIFICATE OF COMPLETION, AGREEING THEY |
| | WILL WORK TOGETHER TO ACHIEVE CODE COMPLIANCE. THESE |
| | DOCUMENTS WILL NEED TO BE SIGNED BY THE QUALIFIER AND |
| | NOTARIZED. |
| | |
| | |
| | 2) SHEET G1.1 INDICATES AN OCCUPANT LOAD OF 84 WHICH |
| | REQUIRES 2 EXITS, SHEET A2.1 INDICATES THE USE OF ONE |
| | EXIT ACCESS IS THROUGH THE STOCK ROOM. THE 2010 FBC-B |
| | 1015.2 EGRESS THROUGH INTERVENING ROOMS DOES ALLOW WITH |
| | EXCEPTION # 2 EGRESS THROUGH STOCKROOMS IN MERCANTILE |
| | OCCUPANCIES WHEN THE FOLLOWING ARE MET: |
| | 1014.2 EXEPTION # 2. MEANS OF EGRESS ARE NOT PROHIBITED |
| | THROUGH STOCKROOMS IN GROUP M OCCUPANCIES WHEN ALL OF |
| | THE FOLLOWING ARE MET: |
| | |
| | 2.1. THE STOCK IS OF THE SAME HAZARD CLASSIFICATION AS |
| | THAT FOUND IN THE MAIN RETAIL AREA; |
| | |
| | 2.2. NOT MORE THAN 50 PERCENT OF THE EXIT ACCESS IS |
| | THROUGH THE STOCKROOM; |
| | |
| | 2.3. THE STOCKROOM IS NOT SUBJECT TO LOCKING FROM THE |
| | EGRESS SIDE; AND |
| | |
| | 2.4. THERE IS A DEMARCATED, MINIMUM 44-INCH-WIDE (1118 |
| | MM) AISLE DEFINED BY FULL- OR PARTIAL-HEIGHT FIXED |
| | WALLS OR SIMILAR CONSTRUCTION THAT WILL MAINTAIN THE |
| | REQUIRED WIDTH AND LEAD DIRECTLY FROM THE RETAIL AREA |
| | TO THE EXIT WITHOUT OBSTRUCTIONS. |
| | |
| | 3) A10.1 THE ACCESSIBLE DRESSING OR FITTING ROOM |
| | INDICATES HANG BARS MOUNTED AT 5'-6" ABOVE THE FLOOR, |
| | PLEASE REVIEW 2010 FBC-ACCESSIBILITY 803.5 COAT HOOKS |
| | AND SHELVING. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |