| 2014-07-01 12:32:08 | BUILDING PLAN REVIEW |
| | PERMIT: 13100297 BOILER BLDG VERTICAL |
| | ADD: 6651 N JOG RD |
| | CONT: KBR |
| | TEL: (561 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 3RD REVIEW |
| | DATE: TUES. JULY 01/ 2014 |
| | ACTION: DENIED |
| | |
| | 1) SHEET 0647 -300-S6-000 THE WIND DESIGN STATES THAT |
| | IT IS DESIGNED TO THE 2010 FBC, THE PLANS DOES NOT |
| | STATE IF THE PRESSURES ARE LISTED AS VULT OR VASD? |
| | PRODUCT APPROVALS ARE LISTED AS VASD. 107.2.1.3 |
| | ADDITIONAL INFORMATION REQUIRED. FOR THE PURPOSE OF |
| | THIS REVIEW IT IS ASSUMED THE PRESSURES ARE VULT, IF |
| | NOT IT IS OF A GREATER CONCERN. |
| | |
| | 2) BOILER ELEVATION SHEET0648-300-S6-550 PROVIDES THE |
| | SPACING OF THE GIRT/ PURLINS AVERAGE BETWEEN 4' & 5' |
| | WITH TTHTE EXCEPTION OF THE |
| | AT ELEVATION 169 TO 178 THE SPACING DROPS TO 3' BETWEEN |
| | PURLINS. THE BUTLER NOA 13-0923.07 BUTLER II WALL PANEL |
| | LIST THE INTERIOR WALL ZONES WITH A 5'-0" SPACING |
| | BETWEEN THE PURLINS, AND AT THE CORNER ZONES A 2'-6" |
| | SPACING. ALSO THE PRESSURES ARE LOW EVEN WHEN AND IF |
| | THE ASSUMED PRESSURES ARE VULT EVEN AT VASD THEY ARE |
| | LOW. |
| | |
| | 3) THE PRODUCT APPROVAL SUBMITTED BUTLER FL 12760 |
| | BUTLER II LITE PANEL PRESSURES ARE A VASD +52.5/ 52.5 |
| | VIEW A INDICATES THAT INTERMEDIATE GIRTS MAY BE |
| | REQUIRED IF PRESSURES ARE HIGHER. |
| | 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41 |
| | COMPONENTS & CLADDING |
| | |
| | 4) SHEET 0590 300-A2-101 SHOWS WALL LOUVERS, TO DATE NO |
| | PRODUCT APPROVALS WERE SUBMITTED FOR THE STORM PROOF |
| | LOUVERS. |
| | 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41 |
| | COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY |
| | AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF |
| | PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE |
| | PRODUCT APPROVALS: |
| | (31)(A) (C) WALL LOUVERS, |
| | |
| | 5) SHEET 0123-300-S22-026 ROOF REFERANCE SHEET SHOWS |
| | THE GIRTS AT 5'-0" AND 4'-8" O. C. PLEASE REVIEW THE |
| | SUBMITTED PRODUCT APPROVAL FOR THE ROOF STEEL ROOF |
| | PANELS NOA 10-0901.20 SEE SHEET 1 OF 6 THE MAXIMUM |
| | PURLIN SPANS ARE EXCEEDED , DEPENDING ON THE SPACING OF |
| | THE PURLINS THE PRESSURES MAY OR MAY NOT WORK. ALSO THE |
| | PRESSURES ARE LOW EVEN WHEN AND IF THE ASSUMED |
| | PRESSURES ARE VULT EVEN AT VASD THEY ARE LOW. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |