2013-11-26 14:34:266651 NORTH JOG ROAD - BOILER BUILDING
 TRACKING #13100297
 PERMIT #12040748
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SHEET A1-100 IS THE ROOF PLAN; HOWEVER, THERE DO NOT
 APPEAR TO BE ANY ARCHITECTURAL FLOOR/PLATFORM PLANS
 PROVIDED BELOW THE ROOF LEVEL. PROVIDE A LIFE SAFETY
 PLAN SHOWING ALL EXITS, EXIT SIGNS, FIRE RATED WALLS,
 EMERGENCY LIGHTING, TRAVEL DISTANCES, COMMON PATH OF
 TRAVE, FIRE EXTINGUISHERS,L ETC.
  
 CONFIRM BOILER FURNACES ARE NOT OIL-FIRED; OTHERWISE
 PER NFPA 850 SECTION 7.5.1.1 BOILER-FURNACES WITH
 MULTIPLE OIL-FIRED BURNERS OR THAT USE OIL FOR IGNITION
 SHOULD BE PROTECTED WITH AUTOMATIC SPRINKLER, WATER
 SPRAY, FOAM, FOAM-WATER SPRINKLER SYSTEMS, OR
 COMPRESSED AIR FOAM SYSTEMS COVERING THE BURNER FRONT
 OIL HAZARD.
  