2013-11-26 15:19:506651 NORTH JOG ROAD - REFUSE BUILDING
 TRACKING #13100296
 PERMIT #12040748
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 COULD NOT LOCATE A LIFE SAFETY PLAN FOR THE CONTROL
 ROOM.
  
 PER NFPA 101 SECTION 40.2.5.1 ANCILLARY FACILITIES: NEW
 ANCILLARY FACILITIES SHALL BE ARRANGED TO ALLOW TRAVEL
 IN INDEPENDENT DIRECTIONS AFTER LEAVING THE ANCILLARY
 FACILITY SO THAT BOTH MEANS OF EGRESS PATHS DO NOT
 BECOME COMPROMISED BY THE SAME FIRE OR SIMILAR
 EMERGENCY.
  
 A.40.2.5.1.1 ANCILLARY FACILITIES LOCATED WITHIN
 INDUSTRIAL OCCUPANCIES MIGHT INCLUDE ADMINISTRATIVE
 OFFICE, CONTROL, AND EMPLOYEE SERVICE FACILITIES THAT
 ARE INCIDENTAL TO THE PREDOMINANT INDUSTRIAL FUNCTION
 AND ARE OF SUCH SIZE THAT SEPARATE OCCUPANCY
 CLASSIFICATION IS NOT WARRANTED.
  
 40.2.5.1.2 NEW ANCILLARY FACILITIES IN SPECIAL-PURPOSE
 INDUSTRIAL OCCUPANCIES WHERE DELAYED EVACUATION IS
 ANTICIPATED SHALL HAVE NOT LESS THAN A 2-HOUR FIRE
 RESISTANCE?RATED SEPARATION FROM THE PREDOMINANT
 INDUSTRIAL OCCUPANCY, AND SHALL HAVE ONE MEANS OF
 EGRESS THAT IS SEPARATED FROM THE PREDOMINANT
 INDUSTRIAL OCCUPANCY BY 2-HOUR FIRE RESISTANCE-RATED
 CONSTRUCTION.
  