2014-08-12 17:12:306651 NORTH JOG ROAD - 500,000 GALLON FIRE WATER TANK
 TRACKING #13100293
 PERMIT #12040748
 REVIEW COMMENTS - FIRE DEPARTMENT
  
  
 NOTE: DRAWING 700-FP-12 SHOWS THE FIRE PUMP, PUMP
 CONTROLLERS, SUCTION PIPING, ETC; HOWEVER, A SEPARATE
 PERMIT WILL BE NEEDED FOR THIS EQUIPMENT PACKAGE.
 SHEET 700-FP-12: PER NFPA 20 SECTION 5.14.6.3.2, ELBOWS
 AND TEES WITH A CENTERLINE PLANE PARALLEL TO A
 HORIZONTAL SPLIT-CASE PUMP SHAFT SHALL NOT BE PERMITTED
 UNLESS THE DISTANCE BETWEEN THE FLANGES OF THE PUMP
 SUCTION INTAKE AND THE ELBOW AND TEE IS GREATER THAN 10
 TIMES THE SUCTION PIPE DIAMETER.
  