| Plan Review Notes For Permit 13100292 |
| Permit Number |
13100292 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2014-08-12 17:12:30 | 6651 NORTH JOG ROAD - 500,000 GALLON FIRE WATER TANK | | | TRACKING #13100293 | | | PERMIT #12040748 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | | | | NOTE: DRAWING 700-FP-12 SHOWS THE FIRE PUMP, PUMP | | | CONTROLLERS, SUCTION PIPING, ETC; HOWEVER, A SEPARATE | | | PERMIT WILL BE NEEDED FOR THIS EQUIPMENT PACKAGE. | | | SHEET 700-FP-12: PER NFPA 20 SECTION 5.14.6.3.2, ELBOWS | | | AND TEES WITH A CENTERLINE PLANE PARALLEL TO A | | | HORIZONTAL SPLIT-CASE PUMP SHAFT SHALL NOT BE PERMITTED | | | UNLESS THE DISTANCE BETWEEN THE FLANGES OF THE PUMP | | | SUCTION INTAKE AND THE ELBOW AND TEE IS GREATER THAN 10 | | | TIMES THE SUCTION PIPE DIAMETER. | | | | | | WESLEY JOLIN | | | FIRE INVESTIGATOR & INSPECTOR | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 805-6730 |
|