2013-10-10 15:28:43PERMIT #13100233
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 ***PROVISO***
 KITCHEN HOOD SUPPRESSION SYSTEM SHALL BE TIED INTO THE
 BUILDING FIRE ALARM SYSTEM TO INITIATE A GENERAL FIRE
 ALARM CONDITION.
  
 PLANS INDICATE THAT THE MANUAL PULL DEVICE IS JUST
 UNDER 10 FEET FROM THE EXHAUST. PER FBC 904.11.1, A
 MANUAL ACTIVATION DEVICE SHALL BE LOCATED ALONG THE
 EGRESS PATH AND BE A MINIMUM OF 10 FEET AND A MAXIMUM
 OF 20 FEET FROM THE KITCHEN EXHAUST SYSTEM. THE DEVICE
 SHALL BE MOUNTED 42-48 INCHES ABOVE THE FLOOR AND SHALL
 CLEARLY IDENTIFY THE HAZARD PROTECTED.
  
  