| 2013-10-18 10:38:32 | BUILDING PLAN REVIEW |
| | PERMIT:13100229 |
| | ADD: 7100 S DIXIE HWY |
| | CONT: CILAS CONCRETE |
| | TEL: (561)689-3427 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: FRIDAY OCT 18/ 2013 |
| | ACTION: DENIED |
| | |
| | 1) THE PLANS ARE PREPARED BY A DRAFTING SEREVICE AND |
| | ADVERTISING AS SUCH WITH THERE NAME IN THE TITLEBLOCK. |
| | F. S. 481.229 EXCEPTIONS; EXEMPTIONS FROM LICENSURE. |
| | (C) ANY OTHER TYPE OF BUILDING COSTING LESS THAN |
| | $25,000.00 EXCEPT FOR A SCHOOL, AUDITORIUM OR OTHER |
| | BUILDING INTENDED FOR PUBLIC USE. |
| | |
| | 2) PLANS FAIL TO PROVIDE THE LOCATION OF THE WORK TO BE |
| | COMPLETED UNDER THIS PERMIT, NO SITE PLAN, NO FLOOR |
| | PLAN WAS PROVIDED INDICATING THE LOCATION THERE ARE TWO |
| | BUILDINGS ON THIS LOT, AND MORE THAN ONE TENANT SUITE. |
| | WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION SECTION |
| | 107.3.5.1.1 MINIMUM PLAN REVIEW CRITERIA FOR BUILDING. |
| | ASSUMED INTERIOR WALL? |
| | |
| | 3) OCCUPANT LOAD IS NOT KNOWN OR TRAVEL DISTANCE ? WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1, ADMINISTRATION, 2010 EDITION SECTION |
| | 107.3.5.1.1 MINIMUM PLAN REVIEW CRITERIA FOR BUILDING. |
| | |
| | 4) THE SUBMITTED PLAN SHOWS EXIT LIGHTS THAT LEAD FOR |
| | EXITING THROUGH THE STOREROOM EGRESS THROUGH THE |
| | STORAGE ROOM NOT SHOWN NOR COMPLIANCE WITH; |
| | 2010 FBC-B 1014.2 EGRESS THROUGH INTERVENING SPACES |
| | 4. EGRESS SHALL NOT PASS THROUGH KITCHENS, STORAGE |
| | ROOMS, CLOSETS OR SPACES USED FOR SIMILAR PURPOSES. |
| | EXCEPTIONS: |
| | 2. MEANS OF EGRESS ARE NOT PROHIBITED THROUGH |
| | STOCKROOMS IN GROUP M OCCUPANCIES WHEN ALL OF THE |
| | FOLLOWING ARE MET: |
| | |
| | 2.1. THE STOCK IS OF THE SAME HAZARD CLASSIFICATION AS |
| | THAT FOUND IN THE MAIN RETAIL AREA; |
| | |
| | 2.2. NOT MORE THAN 50 PERCENT OF THE EXIT ACCESS IS |
| | THROUGH THE STOCKROOM; |
| | |
| | 2.3. THE STOCKROOM IS NOT SUBJECT TO LOCKING FROM THE |
| | EGRESS SIDE; AND |
| | |
| | 2.4. THERE IS A DEMARCATED, MINIMUM 44-INCH-WIDE (1118 |
| | MM) AISLE DEFINED BY FULL- OR PARTIAL-HEIGHT FIXED |
| | WALLS OR SIMILAR CONSTRUCTION THAT WILL MAINTAIN THE |
| | REQUIRED WIDTH AND LEAD DIRECTLY FROM THE RETAIL AREA |
| | TO THE EXIT WITHOUT OBSTRUCTIONS. |
| | |
| | 5) IS THIS A CHANGE IN OCCUPANCY? * 2010 WEST PALM |
| | BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER |
| | 1, ADMINISTRATION, 2010 EDITION 2012 FBC 107.3.5.1.1 |
| | MINIMUM PLAN REVIEW CRITERIA. |
| | |
| | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |