| Plan Review Notes For Permit 13100208 |
| Permit Number |
13100208 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-10-15 10:07:32 | 2010 FBC / 2008 NEC | | | APPROVED WITH EXCEPTIONS | | | | | | 1) COMPLY WITH NEC 680.8 FOR OVERHEAD CONDUCTOR | | | CLEARANCES. | | | | | | 2) COMPLY WITH NEC 680.26 FOR EQUIPOTENTIAL BONDING. |
|