| Plan Review Notes For Permit 13100173 |
| Permit Number |
13100173 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2014-02-03 15:12:15 | RESIDENTIAL (R3) ADDITION/ALTERATION, THIRD MECHANICAL | | | REVIEW CHECKLIST. | | | CODE; 2010 FBC | | | | | | 1- PROVIDE COMPLETE EQUIPMENT SIZING CALCULATIONS. SEC. | | | 403.6 OF 2010 FBC-ENERGY CONSERVATION. | | | | | | 2- A/C PLAN TO LIST THE EQUIPMENT SPECIFIED ON THE | | | EQUIPMENT SIZING CALCULATIONS. SEC. 103.2.2 OF 2010 | | | FBC-ENERGY CONSERVATION. | | | | | | 3- PROVIDE NAME AND SIGNATURE OF THE PERSON RESPONSIBLE | | | FOR THE A/C PLAN DESIGN. SEC. 107.2.1 CITY AMENDMENTS | | | TO FBC. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 |
|