| Plan Review Notes For Permit 13100173 |
| Permit Number |
13100173 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2013-12-18 16:03:40 | REVIEW BY J SAEZ | | | PX 1328 | | | | | | | | | SEE NOTES FROM PREVIOUS REVIEW, NOT ADDRESSED. FOR YOUR | | | CONVENIENCE, FIRST REVIEW COMMENTS ARE AS FOLLOWS: | | | | | | RESIDENTIAL (R3) ADDITION/ALTERATION, MECHANICAL REVIEW | | | COMMENTS. | | | CODE; 2010 FBC | | | | | | 1- PROVIDE COMPLETE EQUIPMENT SIZING CALCULATIONS. SEC. | | | 403.6 OF 2010 FBC-ENERGY CONSERVATION. | | | | | | 2- A/C PLAN TO LIST THE EQUIPMENT SPECIFIED ON THE | | | EQUIPMENT SIZING CALCULATIONS. SEC. 103.2.2 OF 2010 | | | FBC-ENERGY CONSERVATION. | | | | | | 3- PROVIDE NAME AND SIGNATURE OF THE PERSON RESPONSIBLE | | | FOR THE A/C PLAN DESIGN. SEC. 107.2.1 CITY AMENDMENTS | | | TO FBC. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 | | | |
|