Plan Review Notes
Plan Review Notes For Permit 13100173
Permit Number 13100173
Review Stop E
Sequence Number 1
Notes
Date Text
2013-11-05 14:50:46WITHOUT TRYING TO CREATE A "PUNCH LIST" FOR THE
 ELECTRICAL DRAWINGS, THE FOLLOWING ITEMS WERE NOTED AS
 NEEDING FURTHER ATTENTION AND OR CORRECTION.
 1. AS PER THE MECHANICAL SHEET, THE AHU IS TO BE
 LOCATED INSIDE THE ATTIC, THEREFORE THE REQUIREMENTS OF
 NEC 110.33(B) SHALL BE ADDRESSED AND INCLUDED ON THE
 DRAWINGS
 2. WITHOUT KNOWING EXACTLY WHAT WALLS ARE BEING WORKED
 ON, THE PLACEMENT OF THE ELECTRICAL OUTLETS IS NOT
 CLEARLY MENTIONED. SECTION 210.52 OF THE NEC HAS
 SPECIFIC REQUIREMENTS FOR OUTLET PLACEMENT AND SPACING
 WHICH DOES NOT SEEM TO BE MET ON THE DRAWINGS.
 3. JUST AS THE MENTION OF THE TAMPER-RESISTANT
 RECEPTACLE REQUIREMENTS OF 406.11, THOSE OF 406.8 AND
 THOSE OF 210.12 HAVE TO BE MENTIONED AS WELL.
 4. THE SERVICE RISER DIAGRAM DOES NOT COMPLY WITH THE
 REQUIREMENTS OF NEC 250.56
 5. INDICATE ON THE RISER WHERE THE SERVICE DISCONNECT
 IN RELATION TO THE METER AND MAIN PANEL TO MEET NEC
 230.70
 6. MARK THE LOCATION OF THE ELECTRIC METER AND
 DISCONNECT ON THE FLOOR PLAN AND ELEVATIONS
  
 IF YOU HAVE ANY QUESTIONS, PLEASE FEEL FREE TO CONTACT
 ME AT 561-805-6700.