| Plan Review Notes For Permit 13100173 |
| Permit Number |
13100173 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-11-05 14:50:46 | WITHOUT TRYING TO CREATE A "PUNCH LIST" FOR THE | | | ELECTRICAL DRAWINGS, THE FOLLOWING ITEMS WERE NOTED AS | | | NEEDING FURTHER ATTENTION AND OR CORRECTION. | | | 1. AS PER THE MECHANICAL SHEET, THE AHU IS TO BE | | | LOCATED INSIDE THE ATTIC, THEREFORE THE REQUIREMENTS OF | | | NEC 110.33(B) SHALL BE ADDRESSED AND INCLUDED ON THE | | | DRAWINGS | | | 2. WITHOUT KNOWING EXACTLY WHAT WALLS ARE BEING WORKED | | | ON, THE PLACEMENT OF THE ELECTRICAL OUTLETS IS NOT | | | CLEARLY MENTIONED. SECTION 210.52 OF THE NEC HAS | | | SPECIFIC REQUIREMENTS FOR OUTLET PLACEMENT AND SPACING | | | WHICH DOES NOT SEEM TO BE MET ON THE DRAWINGS. | | | 3. JUST AS THE MENTION OF THE TAMPER-RESISTANT | | | RECEPTACLE REQUIREMENTS OF 406.11, THOSE OF 406.8 AND | | | THOSE OF 210.12 HAVE TO BE MENTIONED AS WELL. | | | 4. THE SERVICE RISER DIAGRAM DOES NOT COMPLY WITH THE | | | REQUIREMENTS OF NEC 250.56 | | | 5. INDICATE ON THE RISER WHERE THE SERVICE DISCONNECT | | | IN RELATION TO THE METER AND MAIN PANEL TO MEET NEC | | | 230.70 | | | 6. MARK THE LOCATION OF THE ELECTRIC METER AND | | | DISCONNECT ON THE FLOOR PLAN AND ELEVATIONS | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE FEEL FREE TO CONTACT | | | ME AT 561-805-6700. |
|