| 2013-10-31 13:43:35 | RESIDENTIAL (R3) ADDITION/ALTERATION, BUILDING REVIEW |
| | COMMENTS. |
| | CODE: 2010 FBC. |
| | |
| | 1- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.) |
| | TO VERIFY IF IMPACT FEES ARE DUE. BRING BACK COUNTY |
| | STAMPED PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE. |
| | REQUIRED BY THE COUNTY IMPACT FEE ORDINANCE OF THE |
| | UNIFIED LAND DEVELOPMENT CODE. |
| | |
| | 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | DCA RULE 9N-3 FOR: |
| | A) SINGLE HUNG WINDOWS. |
| | |
| | B) WINDOW MULLIONS. |
| | |
| | C) ENTRY DOOR AS SHOWN ON PLANS. |
| | |
| | D) ALL EXTERIOR DOORS AS SHOWN ON PLANS. |
| | |
| | E) GLASS BLOCK AS SHOWN ON PLANS. |
| | |
| | F) SHUTTERS AS SHOWN ON PLANS. SEE SOUTH ELEVATION. AND |
| | PROVIDE COMPLETE INSTALLATION SCHEDULE. |
| | |
| | G) HURRICANE SHUTTERS IF DOORS AND WINDOWS DON'T HAVE |
| | HURRICANE IMPACT GLAZING. |
| | |
| | H)ROOF TILE. |
| | |
| | I) ROOF TILE ADHESIVE IF USED FOR TILE FASTENING. SEE |
| | TILE PRODUCT APPROVAL FOR LISTED ADHESIVE. COORDINATE |
| | WITH ITEM #9 BELOW. |
| | |
| | I)PRECAST LINTELS AS SPECIFIED ON PLANS. |
| | |
| | 3- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL THE PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS TO FBC. |
| | |
| | 4- PROVIDE COMPLETE SHUTTERS INSTALLATION SCHEDULE IF |
| | DOORS AND WINDOWS DON'T HAVE HURRICANE IMPACT GLAZING. |
| | SEE CITY SAMPLE. |
| | |
| | 5- BEDROOM #3: SPECIFY TYPE AND SIZE OF EXISTING WINDOW |
| | TO BE BE REPLACED TO VERIFY COMPLIANCE WITH THE EGRESS |
| | REQUIREMENTS. SEC. 604 OF 2010 FBC-EXISTING BUILDING. |
| | |
| | 6- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. |
| | 101.4.3 OF 2010 FBC-ENERGY CONSERVATION. |
| | |
| | 7- NEW DINING ROOM: SPECIFY SAFETY GLASS FOR WINDOW |
| | ADJACENT TO THE EXTERIOR DOOR. SEC. R308.4(2) OF 2010 |
| | FBC-RESIDENTIAL. |
| | |
| | 8- REVISE DETAIL 1/5.1 (SEC. 107.2.1 CITY AMENDMENTS TO |
| | FBC): |
| | A) ROOF FINISH IS NOT SHINGLES. |
| | B) REVISE ROOF SHEATHING NAIL TYPE AND SPACING TO MATCH |
| | SPECIFICATIONS ON PLYWOOD SHEATHING NAILING SCHEDULE ON |
| | SHEET 3.1 |
| | C) FOOTING SIZE TO MATCH FOOTING SIZE SHOWN ON SHEET |
| | 2.1. (NOTE: KEEP IN MIND THE MINIMUM FOOTING DIMENSION |
| | REQUIRED BELOW GRADE AND ABOVE GRADE). |
| | |
| | 9- DESIGNER OF RECORD TO SPECIFY ROOF TILE FASTENING AS |
| | REQUIRED BY SEC. 107.2.1.2 OF CITY AMENDMENTS. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561)805-6712 |