| 2013-11-01 11:18:22 | BUILDING PLAN REVIEW |
| | PERMIT: 13100153 |
| | ADD: 1309 N FLAGLER DR |
| | CONT: WESTBROOKE |
| | TEL: (561)395-4126 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: FRI. NOV 01/2013 |
| | ACTION: DENIED |
| | OCC: I-2 HOSPITAL, BLDG TYPE 1B/ 4 STORY |
| | |
| | 1) SHEET S-1 DETAIL # 10 INDICATES THE CUTTING THROUGH |
| | THE 1 HOUR FIRE ROOF AS PER 2010 FBC-B TABLE 601, THERE |
| | ARE NO FIRE PROOFING DETAILS HOW THE 1 HOUR FIRE RATING |
| | WILL BE MAINTAINED. |
| | |
| | 713.4 HORIZONTAL ASSEMBLIES. |
| | PENETRATIONS OF A FLOOR, FLOOR/CEILING ASSEMBLY OR THE |
| | CEILING MEMBRANE OF A ROOF/CEILING ASSEMBLY NOT |
| | REQUIRED TO BE ENCLOSED IN A SHAFT BY SECTION 708.2 |
| | SHALL BE PROTECTED IN ACCORDANCE WITH SECTIONS 713.4.1 |
| | THROUGH 713.4.2.2. |
| | |
| | 713.4.1 FIRE-RESISTANCE-RATED ASSEMBLIES. |
| | PENETRATIONS OF THE FIRE-RESISTANCE-RATED FLOOR, |
| | FLOOR/CEILING ASSEMBLY OR THE CEILING MEMBRANE OF A |
| | ROOF/CEILING ASSEMBLY SHALL COMPLY WITH SECTIONS |
| | 713.4.1.1 THROUGH 713.4.1.4. PENETRATIONS IN HORIZONTAL |
| | SMOKE BARRIERS SHALL ALSO COMPLY WITH 713.5. |
| | 713.4.1.1 THROUGH PENETRATIONS. |
| | THROUGH PENETRATIONS OF FIRE-RESISTANCE-RATED |
| | HORIZONTAL ASSEMBLIES SHALL COMPLY WITH SECTION |
| | 713.4.1.1.1 OR 713.4.1.1.2. |
| | EXCEPTIONS: |
| | 1. PENETRATIONS BY STEEL, FERROUS OR COPPER CONDUITS, |
| | PIPES, TUBES OR VENTS OR CONCRETE OR MASONRY ITEMS |
| | THROUGH A SINGLE FIRE-RESISTANCE-RATED FLOOR ASSEMBLY |
| | WHERE THE ANNULAR SPACE IS PROTECTED WITH MATERIALS |
| | THAT PREVENT THE PASSAGE OF FLAME AND HOT GASES |
| | SUFFICIENT TO IGNITE COTTON WASTE WHEN SUBJECTED TO |
| | ASTM E 119 OR UL 263 TIME-TEMPERATURE FIRE CONDITIONS |
| | UNDER A MINIMUM POSITIVE PRESSURE DIFFERENTIAL OF 0.01 |
| | INCH (2.49 PA) OF WATER AT THE LOCATION OF THE |
| | PENETRATION FOR THE TIME PERIOD EQUIVALENT TO THE |
| | FIRE-RESISTANCE RATING OF THE CONSTRUCTION PENETRATED. |
| | PENETRATING ITEMS WITH A MAXIMUM 6-INCH (152 MM) |
| | NOMINAL DIAMETER SHALL NOT BE LIMITED TO THE |
| | PENETRATION OF A SINGLE FIRE-RESISTANCE-RATED FLOOR |
| | ASSEMBLY, PROVIDED THE AGGREGATE AREA OF THE OPENINGS |
| | THROUGH THE ASSEMBLY DOES NOT EXCEED 144 SQUARE INCHES |
| | (92 900 MM2) IN ANY 100 SQUARE FEET (9.3 M2) OF FLOOR |
| | AREA. |
| | 2. PENETRATIONS IN A SINGLE CONCRETE FLOOR BY STEEL, |
| | FERROUS OR COPPER CONDUITS, PIPES, TUBES OR VENTS WITH |
| | A MAXIMUM 6-INCH (152 MM) NOMINAL DIAMETER, PROVIDED |
| | THE CONCRETE, GROUT OR MORTAR IS INSTALLED THE FULL |
| | THICKNESS OF THE FLOOR OR THE THICKNESS REQUIRED TO |
| | MAINTAIN THE FIRE-RESISTANCE RATING. THE PENETRATING |
| | ITEMS SHALL NOT BE LIMITED TO THE PENETRATION OF A |
| | SINGLE CONCRETE FLOOR, PROVIDED THE AREA OF THE OPENING |
| | THROUGH EACH FLOOR DOES NOT EXCEED 144 SQUARE INCHES |
| | (92 900 MM2). |
| | 3. PENETRATIONS BY LISTED ELECTRICAL BOXES OF ANY |
| | MATERIAL, PROVIDED SUCH BOXES HAVE BEEN TESTED FOR USE |
| | IN FIRE-RESISTANCE-RATED ASSEMBLIES AND INSTALLED IN |
| | ACCORDANCE WITH THE INSTRUCTIONS INCLUDED IN THE |
| | LISTING. |
| | |
| | |
| | 2) SHEET S1 INDICATES S NEW PREFABRICATED ROOF CURB |
| | WITH A NOA PRODUCT APPROVAL. NONE WERE SUBMITTED. THE |
| | PLANS INDICATE THE NEW ROOF TOP CURB TO BE INSTALLED |
| | BUT NOT WHAT WILL BE ONTOP OF THE ROOFTOP CURB MAKING |
| | THE TRANSITION TO JUST CONDUITS. |
| | |
| | 3) SHEET A1.0 INDICATES THE USE OF EFIS WALL SYSTEMS |
| | PER NOA 11-0606.03 NONE WERE SUBMITTED. |
| | |
| | 4) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |