| 2013-10-23 11:32:48 | BUILDING PLAN REVIEW |
| | PERMIT: 13100146 |
| | ADD: 1751 PALM BEACH LAKES # E119 |
| | CONT: TO BE DETERMINED |
| | TEL: (561 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 1ST REVIEW |
| | DATE: WED. OCT. 23/ 2013 |
| | ACTION: DENIED |
| | |
| | 1) PB OUTLET MALLS: A LETTER FROM THE QUALIFIER OF BOTH |
| | THE SHELL CONTRACTOR (EMJ CORPORATION) AND TENANT |
| | BUILD-OUT CONTRACTOR MUST BE PROVIDED BEFORE TENANT |
| | BUILD-OUT PERMIT CAN BE ISSUED, IF THE TENANT BUILD-OUT |
| | CONTRACTOR WISHES TO START WORK BEFORE THE SHELL WORK |
| | HAS RECEIVED A CERTIFICATE OF COMPLETION, AGREEING THEY |
| | WILL WORK TOGETHER TO ACHIEVE CODE COMPLIANCE. THESE |
| | DOCUMENTS WILL NEED TO BE SIGNED BY THE QUALIFIER AND |
| | NOTARIZED. |
| | |
| | 2) COVER SHEET: |
| | |
| | 2A) CODE ANALYSIS: INDICATES THIS PROJECT WAS DESIGNED |
| | TO THE 2009 IBC, IPC & IMC, THE CURRENT FAMILY OF CODES |
| | WERE ADOPTED STATEWIDE IN FLORIDA MARCH 15/ 2012, 2010 |
| | FLORIDA BUILDING CODE, BUILDING, PLUMBING, MECHANICAL & |
| | FIRE PREVENTION CODE. |
| | |
| | 2B) CODE ANALYSIS INDICATES THE OCCUPANT LOAD IS A |
| | TOTAL OF 203, IN BOTH CASES THE MERCANTILE AND |
| | STOCKROOM THE ACTUAL NUMBER OF OCCUPANTS WAS ROUNDED |
| | DOWN, YOU CAN'T ONLY HAVE A PORTION OF A OCCUPANT, |
| | ALWAYS ROUND UP, 2010 FBC-B 1004.1.1 , TALBE L004.1.1 |
| | AND FL BOAF INFORMAL INTERPRETATION # 5479. |
| | |
| | 3) THE PLANS LACK A LIFE SAFETY SHEET, SHEET A-1 |
| | INDICATES 2 EGRESS DOORS, ONE EXIT PATH WILL BE THROUGH |
| | THE STOCK ROOM PLEASE SHOW COMPLIANCE WITH: |
| | 2010 FBC-B 2010 FBC-B 1014.2 EGRESS THROUGH INTERVENING |
| | SPACES |
| | 1014.2.4. EGRESS SHALL NOT PASS THROUGH KITCHENS, |
| | STORAGE ROOMS, CLOSETS OR SPACES USED FOR SIMILAR |
| | PURPOSES. EXCEPTIONS: |
| | 2. MEANS OF EGRESS ARE NOT PROHIBITED THROUGH |
| | STOCKROOMS IN GROUP M OCCUPANCIES WHEN ALL OF THE |
| | FOLLOWING ARE MET: |
| | |
| | 2.1. THE STOCK IS OF THE SAME HAZARD CLASSIFICATION AS |
| | THAT FOUND IN THE MAIN RETAIL AREA; |
| | |
| | 2.2. NOT MORE THAN 50 PERCENT OF THE EXIT ACCESS IS |
| | THROUGH THE STOCKROOM; |
| | |
| | 2.3. THE STOCKROOM IS NOT SUBJECT TO LOCKING FROM THE |
| | EGRESS SIDE; AND |
| | |
| | 2.4. THERE IS A DEMARCATED, MINIMUM 44-INCH-WIDE (1118 |
| | MM) AISLE DEFINED BY FULL- OR PARTIAL-HEIGHT FIXED |
| | WALLS OR SIMILAR CONSTRUCTION THAT WILL MAINTAIN THE |
| | REQUIRED WIDTH AND LEAD |
| | DIRECTLY FROM THE RETAIL AREA TO THE EXIT WITHOUT |
| | OBSTRUCTIONS. |
| | |
| | 4) PLANS DO NOT INCLUDE ANY DETAILS OF A CASH WRAP THAT |
| | IS ACCESSBILE 2010 FL ACCESSIBILITY CODE 904.4 SALES |
| | AND SERVICE COUNTERS. |
| | SALES COUNTERS AND SERVICE COUNTERS SHALL COMPLY WITH |
| | 904.4.1 OR 904.4.2. THE ACCESSIBLE PORTION OF THE |
| | COUNTER TOP SHALL EXTEND THE SAME DEPTH AS THE SALES OR |
| | SERVICE COUNTER TOP. |
| | |
| | EXCEPTION: IN ALTERATIONS, WHEN THE PROVISION OF A |
| | COUNTER COMPLYING WITH 904.4 WOULD RESULT IN A |
| | REDUCTION OF THE NUMBER OF EXISTING COUNTERS AT WORK |
| | STATIONS OR A REDUCTION OF THE NUMBER OF EXISTING MAIL |
| | BOXES, THE COUNTER SHALL BE PERMITTED TO HAVE A PORTION |
| | WHICH IS 24 INCHES (610 MM) LONG MINIMUM COMPLYING WITH |
| | 904.4.1 PROVIDED THAT THE REQUIRED CLEAR FLOOR OR |
| | GROUND SPACE IS CENTERED ON THE ACCESSIBLE LENGTH OF |
| | THE COUNTER. |
| | |
| | |
| | 5) SHEET A-1 INDICATE WITHIN THE ACCESSIBLE DRESSING |
| | ROOM A HANGING RACK BUT NO HEIGHT DIMENSIONS. 2010 FL |
| | ACCESSIBLITY CODE, REACH RANGES AND 803.5 COAT HOOKS |
| | AND SHELVES. |
| | COAT HOOKS PROVIDED WITHIN THE ROOM SHALL BE LOCATED |
| | WITHIN ONE OF THE REACH RANGES SPECIFIED IN 308. |
| | SHELVES SHALL BE 40 INCHES (1015 MM) MINIMUM AND 48 |
| | INCHES (1220 MM) MAXIMUM ABOVE THE FINISH FLOOR OR |
| | GROUND. |
| | |
| | 6) PLEASE PROVIDE CODE COMPLIANCE WITH 2010 FBC-B 713.6 |
| | FIRE WALLS, FIRE BARRIERS, FIRE PARTITIONS, SMOKE |
| | BARRIERS AND SMOKE PARTITIONS OR ANY OTHER WALL |
| | REQUIRED TO HAVE PROTECTED OPENINGS SHALL BE |
| | EFFECTIVELY AND PERMANENTLY IDENTIFIED WITH SIGNS OR |
| | STENCILING IN A MANNER ACCEPTABLE TO THE AUTHORITY |
| | HAVING JURISDICTION. SUCH IDENTIFICATION SHALL BE ABOVE |
| | ANY DECORATIVE CEILING AND IN CONCEALED SPACES. |
| | SUGGESTED WORDING FOR FIRE AND SMOKE BARRIERS: ?FIRE |
| | AND SMOKE BARRIER ? PROTECT ALL OPENINGS.? |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |