2013-10-23 11:32:48BUILDING PLAN REVIEW
 PERMIT: 13100146
 ADD: 1751 PALM BEACH LAKES # E119
 CONT: TO BE DETERMINED
 TEL: (561
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 1ST REVIEW
 DATE: WED. OCT. 23/ 2013
 ACTION: DENIED
  
 1) PB OUTLET MALLS: A LETTER FROM THE QUALIFIER OF BOTH
 THE SHELL CONTRACTOR (EMJ CORPORATION) AND TENANT
 BUILD-OUT CONTRACTOR MUST BE PROVIDED BEFORE TENANT
 BUILD-OUT PERMIT CAN BE ISSUED, IF THE TENANT BUILD-OUT
 CONTRACTOR WISHES TO START WORK BEFORE THE SHELL WORK
 HAS RECEIVED A CERTIFICATE OF COMPLETION, AGREEING THEY
 WILL WORK TOGETHER TO ACHIEVE CODE COMPLIANCE. THESE
 DOCUMENTS WILL NEED TO BE SIGNED BY THE QUALIFIER AND
 NOTARIZED.
  
 2) COVER SHEET:
  
 2A) CODE ANALYSIS: INDICATES THIS PROJECT WAS DESIGNED
 TO THE 2009 IBC, IPC & IMC, THE CURRENT FAMILY OF CODES
 WERE ADOPTED STATEWIDE IN FLORIDA MARCH 15/ 2012, 2010
 FLORIDA BUILDING CODE, BUILDING, PLUMBING, MECHANICAL &
 FIRE PREVENTION CODE.
  
 2B) CODE ANALYSIS INDICATES THE OCCUPANT LOAD IS A
 TOTAL OF 203, IN BOTH CASES THE MERCANTILE AND
 STOCKROOM THE ACTUAL NUMBER OF OCCUPANTS WAS ROUNDED
 DOWN, YOU CAN'T ONLY HAVE A PORTION OF A OCCUPANT,
 ALWAYS ROUND UP, 2010 FBC-B 1004.1.1 , TALBE L004.1.1
 AND FL BOAF INFORMAL INTERPRETATION # 5479.
  
 3) THE PLANS LACK A LIFE SAFETY SHEET, SHEET A-1
 INDICATES 2 EGRESS DOORS, ONE EXIT PATH WILL BE THROUGH
 THE STOCK ROOM PLEASE SHOW COMPLIANCE WITH:
 2010 FBC-B 2010 FBC-B 1014.2 EGRESS THROUGH INTERVENING
 SPACES
 1014.2.4. EGRESS SHALL NOT PASS THROUGH KITCHENS,
 STORAGE ROOMS, CLOSETS OR SPACES USED FOR SIMILAR
 PURPOSES. EXCEPTIONS:
 2. MEANS OF EGRESS ARE NOT PROHIBITED THROUGH
 STOCKROOMS IN GROUP M OCCUPANCIES WHEN ALL OF THE
 FOLLOWING ARE MET:
  
 2.1. THE STOCK IS OF THE SAME HAZARD CLASSIFICATION AS
 THAT FOUND IN THE MAIN RETAIL AREA;
  
 2.2. NOT MORE THAN 50 PERCENT OF THE EXIT ACCESS IS
 THROUGH THE STOCKROOM;
  
 2.3. THE STOCKROOM IS NOT SUBJECT TO LOCKING FROM THE
 EGRESS SIDE; AND
  
 2.4. THERE IS A DEMARCATED, MINIMUM 44-INCH-WIDE (1118
 MM) AISLE DEFINED BY FULL- OR PARTIAL-HEIGHT FIXED
 WALLS OR SIMILAR CONSTRUCTION THAT WILL MAINTAIN THE
 REQUIRED WIDTH AND LEAD
 DIRECTLY FROM THE RETAIL AREA TO THE EXIT WITHOUT
 OBSTRUCTIONS.
  
 4) PLANS DO NOT INCLUDE ANY DETAILS OF A CASH WRAP THAT
 IS ACCESSBILE 2010 FL ACCESSIBILITY CODE 904.4 SALES
 AND SERVICE COUNTERS.
 SALES COUNTERS AND SERVICE COUNTERS SHALL COMPLY WITH
 904.4.1 OR 904.4.2. THE ACCESSIBLE PORTION OF THE
 COUNTER TOP SHALL EXTEND THE SAME DEPTH AS THE SALES OR
 SERVICE COUNTER TOP.
  
 EXCEPTION: IN ALTERATIONS, WHEN THE PROVISION OF A
 COUNTER COMPLYING WITH 904.4 WOULD RESULT IN A
 REDUCTION OF THE NUMBER OF EXISTING COUNTERS AT WORK
 STATIONS OR A REDUCTION OF THE NUMBER OF EXISTING MAIL
 BOXES, THE COUNTER SHALL BE PERMITTED TO HAVE A PORTION
 WHICH IS 24 INCHES (610 MM) LONG MINIMUM COMPLYING WITH
 904.4.1 PROVIDED THAT THE REQUIRED CLEAR FLOOR OR
 GROUND SPACE IS CENTERED ON THE ACCESSIBLE LENGTH OF
 THE COUNTER.
  
  
 5) SHEET A-1 INDICATE WITHIN THE ACCESSIBLE DRESSING
 ROOM A HANGING RACK BUT NO HEIGHT DIMENSIONS. 2010 FL
 ACCESSIBLITY CODE, REACH RANGES AND 803.5 COAT HOOKS
 AND SHELVES.
 COAT HOOKS PROVIDED WITHIN THE ROOM SHALL BE LOCATED
 WITHIN ONE OF THE REACH RANGES SPECIFIED IN 308.
 SHELVES SHALL BE 40 INCHES (1015 MM) MINIMUM AND 48
 INCHES (1220 MM) MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND.
  
 6) PLEASE PROVIDE CODE COMPLIANCE WITH 2010 FBC-B 713.6
 FIRE WALLS, FIRE BARRIERS, FIRE PARTITIONS, SMOKE
 BARRIERS AND SMOKE PARTITIONS OR ANY OTHER WALL
 REQUIRED TO HAVE PROTECTED OPENINGS SHALL BE
 EFFECTIVELY AND PERMANENTLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE AUTHORITY
 HAVING JURISDICTION. SUCH IDENTIFICATION SHALL BE ABOVE
 ANY DECORATIVE CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING FOR FIRE AND SMOKE BARRIERS: ?FIRE
 AND SMOKE BARRIER ? PROTECT ALL OPENINGS.?
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  