| Plan Review Notes For Permit 13100140 |
| Permit Number |
13100140 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-10-31 16:38:04 | THE ELECTRICAL PORTION OF THIS PERMIT HAS BEEN APPROVED | | | WITH THE FOLLOWING NOTATIONS: | | | 1. THE SUBMITTED DRAWING FAIL TO INCLUDE THE OUTLET | | | REQUIRED IN NEC 210.52(C)(2), IN THE ISLAND KITCHEN. | | | 2. BECAUSE YOU HAS FOSSIL FUEL BURNING (GAS) | | | APPLIANCES, FBC REQUIRES THAT YOU INSTALL CARBON | | | MONOXIDE DETECTORS WITHIN 10' OF ANY SLEEPING AREA. | | | 3. ACCORDING TO THE SUBMITTED DRAWING, THE SPACING OF | | | THE EXISTING ELECTRICAL OUTLETS IS NOT COMPLIANT WITH | | | CODE STANDARDS. | | | 3. THIS IS A LEVEL 2 ALTERATION AS PER THE FBC-EXISTING | | | BUILDING, AND THEREFORE YOU WILL NOT BE REQUIRED TO | | | COME INTO COMPLIANCE WITH THE SPACING UNLESS YOU OPEN | | | AND/OR ALTER THE WALL IN QUESTION. | | | 4. ALL WORK SHALL COMPLY WITH THE 2008 EDITION OF THE | | | NEC. | | | | | | SENT TO SH DESK |
|