2013-10-16 07:18:37BUILDING PLAN REVIEW
 PERMIT: 13100134
 ADD: 1855 PALM BEACH LAKES BLDG "B2-FOUNDATION"
 CONT: EMJ
 TEL: (423)855-6857
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 1ST REVIEW
 DATE: WED. OCT 16/2013
 ACTION: DENIED
  
  
 1) SHEET S001. MISSING THE SOILS REPORT WHICH WILL
 PROVIDE THE SAFE MINIMUM BEARING VALUE. 2010 FBC-B
 1803.5.2 QUESTIONABLE SOIL. WHERE THE CLASSIFICATION,
 STRENGTH OR COMPRESSIBILITY OF THE SOIL IS IN DOUBT OR
 WHERE A LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED
 IN THIS CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL BE
 PERMITTED TO REQUIRE THAT A GEOTECHNICAL INVESTIGATION
 BE CONDUCTED.
 PLEASE PROVIDE THE SOILS REPORT FROM ESC DATE JUNE 16,
 2012 PROJECT NUMBER: 25-1847-C.
  
 2) SHEET S001. THIS SWHEET INDICATES THIS BUILDING TO
 BE TILT WALL CONCRETE WALL PANEL CONSTRUCTION, THIS
 TYPE OF CONSTRUCTION REQUIRES A RESIDENT INSPECTOR PER
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION SECTION
 110.3.9. PLEASE CONTACT THE MANAGER OF THE RESIDENT
 INSPECTOR PROGRAM KEN CONRAD FOR FORMS AND OTHER
 IMPORTANT REQUIREMENTS THAT WILL NEED TO BE MET BEFORE
 PERMIT ISSUANCE.
 MANAGER OF RESIDENT INSPECTOR PROGRAM: KEN CONRAD
 TEL 561-805-6666
 E-MAIL: [email protected]
  
 3) FOUNDATIONDETAIL PLAN S501 FOUNDATION DETAIL # 4
 INDICATES TILT WALL PANELS BUT THE PLANS DO NOT
 INDICATE EMBEDS FOR TILT WALL CONSTRUCTION NEITHER DOES
 S101 OR S102.
  
 4) THERE IS NO SITE PLAN PROVIDING THE LOCATION OF THIS
 BUILDING, NO DIMENSION LINES TO PROPERTY LINES OR
 ASSUMED PROPERTY LINES BETWEEN BUILDINGS OR NO MINIMUM
 BUILDING TYPE PROVIDED,
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 107.3.5.1.1. COMMERCIAL BUILDINGS, MINIMUM PLAN REVIEW
 CRITERIA.
  
 5) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676