2014-02-10 15:12:14FOR DESERT LETS ADD THE FOLLOWING TO THE PLANS:
 1. THE DRAIN PUMP CIRCUIT AND CORRESPONDING LOAD SHALL
 BE INCLUDED IN TO PANEL H.
 THE WATER HEATER OVERFLOW AS WELL AS THE WASHING
 MACHINE DRAIN BELOW THE SEWER TAP AND THEREFORE NEEDS
 TO BE PUMPED UP FOR PROPER DRAINAGE.
 2. FACP DEDICATED CIRCUIT AND THE ASSOCIATED
 REQUIREMENTS ARE NOT ADDRESSED ON THE REVISED PLANS.