2014-10-20 14:13:441) SUBMIT COPIES OF THE APPLICABLE SIZING TABLES USED
 FOR THE SIZING OF THIS SYSYTEM. WPB AMEND. TO 2010 FBC
 SEC. 107.2.1.
 2) SHOW THE LONGEST LENGTH OF PIPING FROM THE POINT OF
 DELIVERY TO THE MOST REMOTE OUTLET AND SHOW THE TOTAL
 BTU LOAD ON THE SYSTEM. 2010 FGC SEC.402.4.1.
 3) IDENTIFY THE APPLIANCES ON THE SYSTEM.WPB AMEND. TO
 2010 FBC SEC. 107.2.1.
 4) SHOW THE PSI OF THE SYSTEM ON THE PLANWPB AMEND. TO
 2010 FBC SEC. 107.2.1.
 5) SOME OF THE BTU LOADS ARE ILLEGIBLE.WPB AMEND. TO
 2010 FBC SEC. 107.2.1.
 6) SHOW THE CORRESPONDING EHD FOR THE CSST PIPING. WPB
 AMEND. TO 2010 FBC SEC. 107.2.1.
 7) SOME OF THE INFO ON THE TOP OF THE PIPNG PLAN IS CUT
 OFF.
 8) DETAILS # 1 & #2 - WHAT IS THE 75,000 BTU LOAD AT
 THE TOP OF THE PAGE FOR? THE PIPING PLAN SHOWS THE
 DETAILS AS 150,000 BTU'S.
 9) WHAT DOES DETAIL # 1 & # 2 REPRESENT? WHAT TYPE OF
 APPLIANCE IS THIS?
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
2014-03-05 10:59:17RESTAMP
2014-02-25 14:13:082/25/2014
 THIS REVIEW WILL NOT CONTINUE:
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  